Hazardous Area Application
Associated apparatus may include amplifiers and barriers to monitor apparatus supply current, which is the apparatus output signal. Associated apparatus must limit both
supply voltage and supply current in the event of failures.

Installation Notes

Hazardous Area Application
Entity Parameters: Associated Apparatus may include amplifiers and barriers to monitor apparatus supply current, which is the apparatus output signal. Associated appara-
tus must limit both supply voltage and supply current in the event of failures.

CAUTION: Special Conditions for Safe Use: Parts of the Enclosure are non-conducting and may generate an ignition- capable level
of ESD. Cleaning of the equipment shall be done only with a damp cloth.

Associated Apparatus

Sensor Apparatus

Voc ≤ 15V dc
Isc ≤ 60 mA
Ca ≥ C(cable) + Ci
La ≥ L(cable) + Li

Cable Parameters (if unknown)
C(cable) = 60 pF/ft.
L(cable) = 0.2 μH/ft.

Vmax = 15V dc
Imax = 60 mA
Ci = 0.3 μF

Li = 0
Pi = 225 mW

FM Installation

1. Associated Apparatus (barrier) entity parameters must meet the following requirements:

Voc ≤ Vmax
Isc ≤ Imax
Ca ≥ Ci + Ccable
La ≥ Li + Lcable

2. The Associated Apparatus shall not be connected to any device that uses or generates in excess of 250 Volts rms or dc.
3. Intrinsic safety ground, if required for the Associated Apparatus, shall be less than 1 ohm.
4. Installation shall be in accordance with the National Electrical Code (ANSI/NFPA70), local codes, Associated Apparatus manufacturer’s installation requirements and

ANSI/ISA RP12.6 for hazardous (classified) location installation.

5. Associated Apparatus is not required for installation of the devices within a Division 2 hazardous (classified) location. The maximum voltage for Division 2 installation

is 15V dc.

6. Maximum connector torque: 6 ft-lbs.

CSA Installation

1. Associated Apparatus (barrier) entity parameters must meet the following requirements:

Voc ≤ Vmax
Isc ≤ Imax
Ca ≥ Ci + Ccable
La ≥ Li + Lcable

2. The Associated Apparatus shall not be connected to any device that uses or generates in excess of 250 Volts rms or dc.
3. Intrinsic safety ground, if required for the Associated Apparatus, shall be less than 1 ohm.
4. Installation shall be in accordance with the Canadian Electrical Code, Part 1.
5. Associated Apparatus (barrier) shall be installed in accordance with the manufacturer’s instructions.
6. Associated Apparatus is not required for installation of the devices within a Division 2 hazardous (classified) location when installed in, or through the wall of a

suitable enclosure with provision for connection of rigid metal conduit per the Canadian Electrical Code, as acceptable to the local inspection authority having juris-
diction. The maximum rating for Division 2 installation is 15V dc, 60 mA.

7. In Division 2 installations, observe the following warning.