Sensor programming, Teaching minimum and maximum limits – Banner U-GAGE QT50U Ultrasonic Sensors User Manual

Page 4

Advertising
background image

Sensor Programming

Two TEACH methods may be used to program the sensor, using the TEACH button:

Teach individual minimum and maximum limits.

Use the Auto-Window feature to center a sensing window around the taught position.

A

B

C

D

E

F

Figure 3. Sensor features

A - TEACH button
B - Sensor power indicator
C - Target signal strength indicator
D - Speed button
E - Output response time indicator
F - Output ON indicator

Teaching Minimum and Maximum Limits

Output OFF

Output ON

Output OFF

Minimum

Limit

Maximum

Limit

Output ON

Output ON

Output OFF

Minimum

Limit

Maximum

Limit

Normally Closed Output

Normally Open Output

Figure 4. Teaching independent minimum and maximum limits —

window limit models

Teach procedures are identical for window-limit and fill-

level control models. Window-limit models function as

shown in the figure on the right, and fill-level control

models function as shown in

Figure 5

on page 5. To

readjust minimum or maximum limits, repeat the teach

procedure.

A button click is defined as: 0.04 s. ≤ Click ≤ 0.8 s.

1. Enter programming mode.

Action

Result

Push and hold TEACH button for 2 seconds

Output LED turns solid red and the sensor waits for first limit

2. Teach the first limit.

Action

Result

Position the target for the first limit.

Click the TEACH button.

The sensor learns the first limit position and the Output LED

changes to flashing red

3. Teach the second limit.

U-GAGE QT50UVR Series Sensors

4

www.bannerengineering.com - tel: 763-544-3164

P/N 117764 Rev. F

Advertising