Banner Q45 Namur DC Series User Manual

Page 9

Advertising
background image

Mounting Brackets

Hole center spacing: A = 51, A to B = 25.4
Hole size: A = 42.6 x 7, B = ø 6.4, C = ø 30.1

Hole center spacing: A to B=31.8, B to C=19.0, A to C=50.8,
D=50.8
Hole size: C=6.9x32, D=73.0x6.9

Q45 NAMUR Sensors Certification Notes

Quick-Disconnect (Q-suffix) Sensor, Connector View

Wiring: Cabled and Quick-Disconnect (Q-suffix) Models

Front of Sensor

POWER SOURCE

and

SENSOR MONITOR

INTRINSIC SAFETY GROUND

(if required)

NON-HAZARDOUS AREA

HAZARDOUS AREA

BROWN

BLUE

+

NAMUR SENSOR

DIN 19234

FACTORY MUTUAL APPROVED

ASSOCIATED APPARATUS

APPARATUS

Hazardous Area Application
Entity Parameters
. Associated Apparatus may include amplifiers and barriers to monitor apparatus supply current which is the appara-
tus output signal. Associated apparatus must limit both supply voltage and supply current in the event of failures.

Entity Parameters

Associated Apparatus

Sensor Apparatus

Voc ≤ 15V dc

Vmax = 15V dc

Isc ≤ 60 mA

Imax = 60 mA

Ca ≥ *C (cable) + Ci

Ci = 0.3 µF

La ≥ *L (cable) + Li

Li = 0

Pi = 225 mW

Cable Parameters (if unknown)

*C(cable) = 60 pF/ft

*L(cable) = 0.2 μH/ft

FM Installation Notes
a) Associated Apparatus (barrier) entity parameters must meet the following requirements:

• Voc ≤ Vmax
• Ca ≥ Ci + Ccable
• Isc ≤ Imax
• La ≥ Li + Lcable

b) The Associated Apparatus shall not be connected to any device that uses or generates in excess of 250 Volts rms or dc.
c) Intrinsic safety ground, if required for the Associated Apparatus, shall be less than 1 ohm.
d) Installation shall be in accordance with the National Electrical Code (ANSI/NFPA70), local codes, Associated Apparatus manufactur-
er’s installation requirements and ANSI/ISA RP12.6 for hazardous (classified) location installation.

Q45 NAMUR Sensors

P/N 038343 Rev. H

www.bannerengineering.com - tel: 763-544-3164

9