Dimensions, Hookups – Banner T30 Series User Manual
Page 4

Dimensions
Cabled Models
QD Models
11.5 mm
(0.45")
66.5 mm
(2.62")
Red LED
Alignment Indicator
Jam Nut
(Supplied)
M30 x 1.5
Thread
ø 15 mm
(0.59")
ø 40.0 mm
(1.57")
45.0 mm
(1.77")
51.5 mm
(2.03")
Hookups
Cabled Models
Quick-Disconnect Models
NAMUR Sensor
Hazardous Area
≤ 15V dc
Power
Output
Sensor
Input
Non-hazardous Area
Associated Apparatus
br
bu
+
–
+
–
NAMUR Sensor
Hazardous Area
1
≤ 15V dc
Power
Output
Sensor
Input
Non-hazardous Area
Associated Apparatus
2
br
bu
3
4
+
–
+
–
Entity Parameters
Associated Apparatus
Voc ≤ 15V dc
Isc ≤ 35 mA
Ca ≥ *C (cable) + Ci
La ≥ *L (cable) + Li
Sensor Apparatus
Vmax = 30V dc
Imax = 35 mA
Ci = 0
Li = 0
Pi = 131
*C (cable) = 60 pF/ft
*L (cable) = 0.2 uH/ft
Important: Hazardous Area Application
Associated apparatus may include amplifiers and barriers to monitor apparatus supply current which is the apparatus output signal.
Associated apparatus must limit both supply voltage current in the even of failures.
T30 Series NAMUR Fixed-Field Sensors
4
www.bannerengineering.com - tel: 763-544-3164
P/N 041685 Rev. B