View Menu (1 of 2)

The View menu items display the current operating temperatures and status information of the system.

Item Field

Range

Access

Description

Set to

1 to 12

User

Installer

SNOW ZONE

The snow melt zone number on the tekmarNet

®

system.
Conditions: tekmarNet

®

communication available.

– – –, -76 to

149°F

(-60 to 65°C)

User

Installer

OUTDOOR

Current outdoor air temperature as measured by the local
or remote outdoor sensor. The outdoor air temperature is
shared to all devices in the tekmarNet

®

system. “– – –” is

displayed when no outdoor sensor is available.
Conditions: Application Mode is set to PWM, Boil, Mix or
Elec.

– – –, -76 to

149°F

(-60 to 65°C)

Installer

SLAB TARGET

The calculated slab target of the snow melting system.
“– – –” is displayed when the snow melt control is off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.

-76 to 149°F

(-60 to 65°C)

User

Installer

SLAB

Current slab temperature as measured by the control.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.

DRY or WET

User

Installer

WATER SENSOR

Current status of the water detection sensor.
Conditions: A snow/ice sensor or snow sensor is installed.

---, 70 to 200°F

(21.0 to 93.5°C)

Installer

BOILER TARGET

The calculated boiler target of the snow melt system.
“– – –” is displayed when the snow melt control is not operating
the boiler.
Conditions: Application Mode is set to Boil.

---, 70 to 200°F

(21.0 to 93.5°C)

Installer

MIX TARGET

The calculated mix target of the snow melt system. “– – –”
is displayed when the snow melt control is not operating the
mixing valve or mixing injection pump.
Conditions: Application Mode is set to Mix.

-58 to 212°F

(50.0 to 100.5°C)

Installer

SUPPLY

Current system supply temperature as measured by the
control.
Conditions: Application Mode is set to PWM, Boil or Mix.

-58 to 212°F

(50.0 to 100.5°C)

Installer

BOILER RETURN

Current boiler return temperature as measured by the
control.
Conditions: Application Mode is set to PWM, Boil or Mix and
Out/Bret Sensor is set to Bret (boiler return sensor).

0 to 100%

Installer

MIX RATE

Current position of the mixing valve or mixing injection
pump speed.
Conditions: Application Mode is set to Mix.

0 to 100%

Installer

BOILER RATE

Current firing rate of the modulating boiler.
Conditions: Application Mode is set to Boil and Boiler Type
is set to Mod (modulating boiler).