The Boiler Menu provides settings on how to configure and operate the boiler.

Boiler Menu

Item Field

Range

Access

Description

Set to

App Mode = Boil

MOD, 1STG,

EMS1, EMS2

Default = MOD

App Mode = Mix

OFF, ENBL,

CTRL

Default = OFF

App Mode = PWM

OFF, CTRL

Default = OFF

Installer

BOILER TYPE

The type of boiler connected to the control.
MOD = Modulating boiler.
1STG = Single one-stage on-off boiler.
EMS1 = tekmar boiler staging controls.
EMS2 = Viessmann modulating boilers with 0-10 V
OpenTherm Module.
CTRL = tekmarNet

®

System Control operates boiler.

ENBL = When operating a mixing valve or mixing
injection pump, the heat relay is closed to fire the
boiler.

0-10 or 4-20

Default = 0-10

Installer

BOILER MODULATION TYPE

Select if the modulating boiler accepts a 0-10 V (dc) or
4-20 mA input signal to control the boiler firing rate.
Conditions: Boiler Type is set to MOD (modulating
boiler).

0 to 50%

Default = 0%

Installer

BOILER MINIMUM MODULATION

The minimum percent modulation of the boiler burner.
Conditions: Boiler Type is set to MOD (modulating
boiler).

OFF, 10 to 180

seconds

Default = OFF

Installer

BOILER MODULATION DELAY

Delay time between the burner firing and the boiler
releasing to modulation.
Conditions: Boiler Type is set to MOD (modulating
boiler).

30 to 230 seconds

Default = 30 seconds

Installer

BOILER MOTOR SPEED

The time required for the modulating actuating motor to
fully open the gas valve or ramp the burner fan from off to
full speed on a modulating boiler. Set to 30 seconds unless
otherwise recommended by the boiler manufacturer.
Conditions: Boiler Type is set to MOD (modulating
boiler).

AUTO, 2 to 42°F

(1.0 to 23.5°C)

Default = AUTO

Installer

BOILER DIFFERENTIAL

The temperature differential that the control is to use to
cycle the boiler on and off (half above and half below
target).
Conditions: Boiler Type is set to MOD (modulating boiler)
or 1STG (one stage).

OFF, 50 to 180°F

(10.0 to 82.0°C)

Default = OFF

Installer

BOILER MINIMUM

The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommended supply water
temperatures.
Conditions: Application Mode is set to Boil or Application
Mode is set to Mix and the Boiler Type is set to CTRL (tN4
Control) and Out/Bret Sensor is set to RET (return).