Job record – tekmar 654 Snow Melting Control Installation User Manual

Page 42

Advertising
background image

©

2013 654_D

-

06/13

42

of

44

Symptom

Look For...

Corrective Action

LCD display is
off

Power to control

Use electrical meter to measure 24 V (ac) voltage on input power R and C
terminals.

System pump
always on

Display shows Idle

Idle operation requires that the system pump operate continuously while below the
melting temperature setting.

Blue short

Dirt or salt on snow/
ice sensor

The snow/ice sensor requires regular cleaning. Avoid using road salt on the snow
melting slab.

Slab is
above melt
temperature

Slab Target

The slab is heated to the slab target.

Heat On not shown

Check wiring of the system pump. The system pump operates continously during
melt, idle or storm operation. The heat source must be wired to operate together
with the heat relay.

System running
with no snow

Idle

Idling heats the slab when the temperature falls below the Idle temperature.

Melt

During cold weather cut out (CWCO), the system is shut off. If shut off during a
melt cycle, the system resumes melting once the outdoor temperature is above
CWCO.

Timed Melt

System manually started.

Sched Melt

System started on a programmable schedule.

Snow on slab
but system did
not start

Off

System has a programmable schedule and is in event 2 or 4 (unoccupied).

Off

System has been manually Stopped and the automatic snow / ice sensor never
dried, thereby preventing the system to automatically start.

Frequently Asked Questions

Item

Setting

EVENT 1

EVENT 2

EVENT 3

EVENT 4

Schedule Menu Settings

Item

Setting

SCHEDULE

EVENT PER DAY

24 HOUR / 7 DAY

Job Record

Item

Setting

UNITS

Display Menu Settings

Item

Setting

BACKLIGHT

Item

Setting

SCENES

Scene Menu Settings

Item

Setting

AWAY KEY

Advertising