Melt - Manual Start and Timed Stop

The snow melting system can be started manually in one of
three different methods:

Touch the Melt key on the control display.
Press the Setpoint Enable button on a User Switch.
Activate through a Gateway webpage or home automation
system.



Touch MELT key

095 detects water

Tracked zone melt

User Switch / Gateway Enable

MANUAL MELT RUN TIME elapses

AWAY scene

Tracked zone time elapses

Touch STOP key

WWSD

User Switch / Gateway Disable

CWCO

Timed

Melt

or

Idle

Off

095 detects water

Press

Melt

Once manually started, the snow melting system continues to
operate until the time set by the Manual Melt Run Time setting
in the Set Temp menu elapses.

If a manual start has been provided and a Snow / Ice Sensor
detects water, the control changes from manual melt to
automatic operation. The snow melting system will continue
to operate until the sensor is dry and the Additional Melt
Time elapses.

Away

Storm

Melt

Press

Melt

tN4 User Switch

480 or 481

Melt - Automatic Start and Stop

Automatic start and stop operation requires the installation
of a Snow / Ice Sensor 090 (65' or 20 m cable) or 094 (210'
or 64 m cable). The control continually monitors the sensor
for the presence of moisture and slab temperature condi-
tions in which snow or ice may be present. When moisture
is detected, the control will show “Sensor Water Wet” in the
View menu. When the sensor is dry the control will show
“Sensor Water Dry”. The control includes a Sensitivity
setting in the Set Temp menu that allows the installer to
adjust the amount of moisture required to start and stop the
melting operation. In areas with low amounts of dust and
/ or air pollution, the sensitivity may need to be increased.
The Sensitivity setting default is Auto, and the control will
automatically determine the best suitable sensitivity setting
for the installation.

Touch STOP key

090 or 094 and slab dry and

ADD MELT time elapses

or

Idle

Off

AWAY scene

WWSD

090 or 094 detects water

Exits

CWCO

Melt

Suspended

Enters

CWCO

Auto

Melt

User Switch / Gateway Disable

When moisture is detected and the slab and outdoor temperatures
are at or below freezing, the control will automatically start the
snow melting system. As the snow or ice melts and the slab dries
off, the sensor also dries off at the same time. When the sensor
is dry, the snow melt system automatically shuts off. If there are
low spots on the slab surface that dry off slower than the sensor,
additional melting run time can be included by adjusting the
Additional Melt Time setting in the Set Temp menu.
If the snow melting system is manually stopped, the Snow / Ice
Sensor must fully dry before it is able to detect a new snow fall
and automatically start the snow melting system.

Snow / Ice Sensor