Control Wiring

Snow / Ice Sensor

090 or 094

Slab

Brn

+

Mod

tN4

Aux Ht

R

C

Bret

Out/

Com

Blk

Yel Blu Red

Sup

No Power

Snow Sensor

095

Slab Sensor
072 or 073

Slab

Brn

+

Mod

tN4

Aux Ht

R

C

Bret

Out/

Com

Blk

Yel Blu Red

Sup

No Power

Snow

Sensor

095

The control requires an external transformer. A tekmar
Transformer 009 can supply up to 40 VA, and includes an
in-line fuse to protect the transformer and control.

The total power capacity of the power supply should be
larger than the total load of all the devices connected to the
control. This total load must not exceed 100 VA.

Sizing the Transformer

Snow / Ice Sensor -------------------------------

-------------------------------

Snow and Slab Sensor --------------------------

--------------------------

Outdoor, Supply and Boiler Return Sensor ------

------

Outdoor

Sensor

070

or

Boiler

Return

Sensor

082

Supply

Sensor

082

Slab

Brn

+

Mod

tN4

Aux Ht

R

C

Bret

Out/

Com

Blk

Yel Blu Red

Sup

No Power

Modulating Output and tN4 Communication -----

-----

Modulating Boiler

Mixing Valve or

Mixing Injection Pump

0-10 V (dc) Signal

tekmarNet

®

4

Communication

+

tN4 C

Slab

Brn

+

Mod

tN4

Aux Ht

R

C

Bret

Out/

Com

Blk

Yel Blu Red

Sup

No Power

See Application Brochure 654_A for specific application wiring diagrams.