Tekmarnet, Menu – tekmar 654 Snow Melting Control Installation User Manual

Page 24

Advertising
background image

©

2013 654_D

-

06/13

24

of

44

Item Field

Range

Access

Description

Set to

Range: AUTO,

01 to 24,

b:01 to b:24,
1:01 to 1:24,
2:01 to 2:24,

3:01 to 3:24

Installer

ADDRESS

The tekmarNet

®

address of this control. To manually set

the address, use the up or down arrow buttons.

1 to 24

Installer

DEVICE COUNT

Provides a count of all the tekmarNet

®

thermostats,

setpoint controls and snow melting controls on the

tekmarNet

®

system.

1 to 12

Default = 1

Installer

SNOW ZONE

Select the Snow Zone that this control operates. Snow

Zone 1 has the highest priority while Snow Zone 12 has

the lowest priority.

OFF or ON

Default = OFF

Installer

TRACK ZONE

Select to track and record the running hours of Snow Zone

1 and repeats this run time on this control. This allows

snow zones without a snow / ice sensor to automatically

start.
Conditions: Snow Zone must be set 2 through 12 (cannot

be Snow Zone 1) and Application Mode is set to PWM,

Boil, Mix or Elec.

1 to 12

Default = 1

Installer

MELT GROUP

A User Switch may be used to manually start melting

the snow zone. Set the Melt Group number to the

corresponding Setpoint Enable number on the User

Switch.
Conditions: Application Mode is set to PWM, Boil, Mix

or Elec.

1 to 12

Default = 12

Installer

STORM GROUP

A User Switch may be used to manually start storm

operation of the snow zone. Set the Melt Group number

to the corresponding Setpoint Enable number on the

User Switch.
Conditions: Application Mode is set to PWM, Boil, Mix

or Elec.

OFF, COND,

FULL

Default = OFF

Installer

PRIORITY

Select the priority operation of the snow melting system.
Conditions: Application Mode is PWM, Mix or Elec.

OFF or ON

Default = OFF

Installer

LOCAL NETWORK GROUP
Select if scenes and time clock are shared when
connected to a tekmarNet

®

system.

OFF = Send and receive messages.
ON = Receive messages only.

Conditions: Application Mode is set to PWM, Boil, Mix

or Elec.

tekmarNet

®

Menu

The tekmarNet

®

menu includes settings of how the snow melting control communicates and operates together with other controls.

The tekmarNet

®

menu is only available when communication is detected.

Advertising