The System Menu provides settings on how to configure and operate the mechanical equipment.

System Menu

Item Field

Range

Access

Description

Set to

PWM, BOIL, MIX,

ELEC, 090

Default = PWM

Installer

APPLICATION MODE

Select the control application mode.
PWM = Hydronic Pulse Width Modulation.
BOIL = Hydronic boiler heats snow melting system.
MIX = Hydronic mixing valve or injection pump heats
snow melting system.
ELEC = Electric snow melt.
090 = Tandem Snow/ Ice Detection using 090 or 094

NONE,

090 (or 094),

095

Default = 090

Installer

SNOW / ICE SENSOR

Select if a Snow / Ice Sensor 090 or 094, or Snow Sensor
095 is installed.

OFF or ON

Default = ON

Installer

SLAB SENSOR
Select if a Slab Sensor 072 or 073 is installed to measure
the slab temperature.
Conditions: Application Mode is set to PWM, Boil or Mix
and Snow / Ice Sensor is set to None or 095.

OFF or ON

Default = ON

Installer

SLAB PROTECTION

Select if the slab should be protected from large
temperature differentials to avoid cracking the concrete
due to high tensile stress.

Conditions: Application Mode is set to Boil or Mix and Snow
/ Ice Sensor is set to 090 or Slab Sensor is set to On.

OFF, OUT

(Outdoor) or

BRET (Boiler Return)

Default = OUT

Installer

OUTDOOR OR BOILER RETURN SENSOR

Select if the Out/Bret wiring terminal is connected to an
outdoor sensor or a boiler return sensor.

Conditions: Application Mode is set to PWM, Boil or
Mix or Elec.

OFF or ON

Default = OFF

Installer

ECONOMELT

EconoMelt allows the user to mechancially remove snow
then manually start the system to melt the thin snow
layer or ice.

Conditions: Application Mode is set to PWM, Boil or
Mix or Elec.

OFF or ON

Default = ON

Installer

tekmarNet

®

SYSTEM PUMP

Select if the system pump located on the tekmarNet

®

System Control should operate when the snow melt
zone is heating.

Conditions: Application Mode is set to PWM, Boil or Mix
and Boiler Type is set to CTRL (tN4 control).

SYS (System Pump)

or

ALRT (Alert)

Default = SYS

Installer

AUXILIARY RELAY

Select if the auxiliary relay should function as system
pump or as an alert.

Conditions: Application Mode is set to PWM, Boil or Mix.

0.5 to 7.0 days, OFF

Default = 3.0 days

Installer

MAXIMUM MELT TIME

Select to limit the amount of melting run time after snow
is automatically detected by a Snow / Ice Sensor 090 or
094, or a Snow Sensor 095.

Conditions: Application Mode is set to PWM, Boil or
Mix or Elec.