The Override Menu allows an operator to manually test each relay and manually start the system.

Override Menu

Item Field

Range

Access

Description

Hydronic

AUTO, HAND,

MAX, PRGE, OFF

Electric

AUTO, HAND,

TEST, OFF

Default = AUTO

Installer

MANUAL OVERRIDE

Manually override the normal automatic operation of the control to test
the equipment or operate the system at the maximum temperature
limits.
AUTO = Normal operation
HAND = Manual override of each relay output
MAX = Operate hydronic system at maximum heat
TEST = Operate electric system for 10 minutes
PRGE = Hydronic system purge operates pumps to help bleed air
from the system

OFF or ON

Default = OFF

Installer

SYSTEM PUMP RELAY

Manually turn on the system pump during the HAND Manual
Override.

OFF or ON

Default = OFF

Installer

HEAT RELAY
Manually turn on the heat during the HAND

Manual Override

.

0 to 100%

Default = 0%

Installer

BOILER PERCENT
Manually set the modulating boiler firing rate during the HAND

Manual Override

.

Conditions: Application Mode is set to Boil.

0 to 100%

Default = 0%

Installer

MIX PERCENT
Manually set the mixing valve or mixing injection pump output during
the HAND

Manual Override

.

Conditions: Application Mode is set to Mix.

OFF or ON

Default = OFF

Installer

ALERT RELAY
Manually turn on the alert relay during the HAND

Manual

Override

.

Conditions: Application Mode is set to PWM, Boil or Mix and Alert
Relay is set to ALRT (alert) or the Application Mode is set to Elec.

0:10 to 72:00

hours

Default = 0:10

hours

Installer

OVERRIDE TIME
Select the amount of time that the HAND

Manual Override

is in effect

before returning to Automatic operation.

0:10 to 72:00

hours

Default = 24:00

hours

Installer

MAXIMUM PURGE TIME
Select the amount of time that the PURGE Manual Override is in
effect before returning to Automatic operation.
Conditions: Application Mode is set to PWM, Boil or Mix.

0:10 to 72:00

hours

Default = 24:00

hours

Installer

MAXIMUM HEAT TIME
Select the amount of time that the MAX HEAT Manual Override is
in effect before returning to Automatic operation.
Conditions: Application Mode is set to PWM, Boil or Mix.