Units with Factory-Installed Disconnect — The factory-

installed disconnect is an interlocking, door-type. The discon-

nect handle locks the door when it is in the ON position. The

disconnect handle must be in the OFF position to open the con-

trol box door. The disconnect is located in a separate control

box behind the control box door for all units. See Fig. 43.

All field wiring must comply with NEC and all local codes.

Wire must be sized based on MCA (Minimum Circuit Amps)

on the unit informative plate. See Fig. 44 for power wiring con-

nections to the unit disconnect and equipment ground.

Operating Voltage — Operating voltage to the compressor

must be within the voltage range indicated on the unit name-

plate. Voltages between phases must be balanced within 2%,

and the current must be balanced within 10%. See Tables 7-16

for unit electrical data.

Use the following formula to determine the percentage of

voltage imbalance.

Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:

= 1.53%

This amount of phase imbalance is satisfactory as it is be-

low the maximum allowable 2%.

Unit failure as a result of operation on improper line voltage

or excessive phase imbalance constitutes abuse and may cause

damage to electrical components.

DISCONNECT SIZE

QUANTITY...MAXIMUM WIRE SIZE

(MCM)

200 Amps
400 Amps
600 Amps

1...300
1...600
2...600

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

455 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

IMPORTANT: If the supply voltage phase imbalance is

more than 2%, contact local utility immediately.

Fig. 39 — Disconnect Location — Size 030-050 Units

CAUTION

Use care when drilling into corner post to avoid damage to con-
denser coil.