Carrier WEATHERMASTER 48ZT User Manual
Page 40
40
Table 7 — Electrical Data, 48ZG,ZN030 Units
LEGEND
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
EXHAUST
FAN
POWER SUPPLY
No. 1
No. 2
RLA
LRA
RLA
LRA
Qty
Total
FLA
Hp
FLA
Total
Hp
Total
FLA
MCA
MOCP
208/230
187-254
53.2
266
53.2
266
2
6.6
(ea)
7
1
/
2
24.2/22.0
—
—/—
157.1/154.9
200/200
6
21.2/19.2
178.3/174.1
225/225
10
33.4/30.4
190.5/185.3
225/225
15
48.4/44.0
205.5/198.9
250/250
20
61.6/56.0
220.8/211.6
250/250
10
30.8/28.0
—
—/—
163.7/160.9
200/200
6
21.2/19.2
184.9/180.1
225/225
10
33.4/30.4
197.1/191.3
250/250
15
48.4/44.0
212.1/204.9
250/250
20
62.0/56.0
227.4/217.6
250/250
15
46.2/42.0
—
—/—
179.1/174.9
225/225
6
21.2/19.2
184.9/180.1
250/225
10
33.4/30.4
197.1/191.3
250/250
15
48.4/44.0
212.1/204.9
250/250
20
62.0/56.0
227.4/217.6
300/250
20
59.4/54.0
—
—/—
193.9/187.1
250/225
6
21.2/19.2
215.1/206.3
250/250
10
33.4/30.4
227.3/217.5
250/250
15
48.4/44.0
242.3/231.1
300/250
20
62.0/56.0
256.0/243.6
300/250
25
74.8/68.0
—
—/—
213.1/204.6
250/225
6
21.2/19.2
234.3/223.8
300/250
10
33.4/30.4
246.5/248.6
300/300
15
48.4/44.0
261.5/248.6
300/300
20
62.0/56.0
274.7/260.6
300/300
460
414-508
28.8
120
28.8
120
2
3.3
(ea)
7
1
/
2
11.0
—
—
82.4
110
6
9.6
92.0
110
10
15.2
97.6
125
15
22.0
104.4
125
20
28.0
110.4
125
10
14.0
—
—
85.4
110
6
9.6
95.0
110
10
15.2
100.6
125
15
22.0
107.4
125
20
28.0
113.4
125
15
21.0
—
—
92.4
110
6
9.6
102.0
125
10
15.2
107.6
125
15
22.0
114.4
125
20
28.0
120.4
125
20
27.0
—
—
98.4
125
6
9.6
108.0
125
10
15.2
113.6
125
15
22.0
120.4
125
20
28.0
126.4
150
25
34.0
—
—
106.7
125
6
9.6
116.3
150
10
15.2
121.9
150
15
22.0
128.7
150
20
28.0
134.7
150
575
518-632
23.1
96
23.1
96
2
2.4
(ea)
7
1
/
2
9.0
—
—
65.8
80
6
7.8
73.6
90
10
12.2
78.0
100
15
18.0
83.8
100
20
22.0
87.8
110
10
11.0
—
—
67.8
90
6
7.8
75.6
90
10
12.2
80.0
100
15
18.0
85.8
100
20
22.0
89.8
110
15
17.0
—
—
73.8
90
6
7.8
81.6
100
10
12.2
86.0
100
15
18.0
91.8
110
20
22.0
95.8
110
20
22.0
—
—
78.8
100
6
7.8
86.6
100
10
12.2
91.0
110
15
18.0
96.8
110
20
22.0
100.8
110
25
27.0
—
—
84.8
110
6
7.8
92.6
110
10
12.2
97.0
110
15
18.0
102.8
125
20
22.0
106.8
125
FLA
— Full Load Amps
Hp
— Nominal Horsepower
IFM
— Indoor (Supply) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps (for wire sizing)
MOCP — Maximum Overcurrent Protection
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps