44

Table 11 — Electrical Data, 48ZG,ZN055 Units

LEGEND

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan
motors rated at 0.3 FLA each.

NOMINAL

VOLTAGE

(3 Ph 60 Hz)

VOLTAGE

RANGE

COMPR

NO. 1

COMPR

NO. 2

OFM

IFM

BASE UNIT

ONLY

EXHAUST

FAN

BASE UNIT WITH

EXHAUST FAN

RLA

LRA

RLA

LRA

Total

FLA

Hp

FLA

MCA

MOCP

Total

Hp

Total

FLA

MCA

MOCP

208/230

187-254

108

506

74.4

345

26.4

15

46.2/42

281.6/277.4

350/350

10

34/30

315.0/307.4

400/400

15

48/44

330.0/321.4

400/400

20

62/56

343.2/333.4

450/400

20

59.4/54

294.8/289.4

400/350

10

34/30

328.2/319.4

400/400

15

48/44

343.2/333.4

450/400

20

62/56

356.4/345.4

450/450

25

74.8/68

310.2/303.4

400/400

10

34/30

343.6/333.4

450/400

15

48/44

358.6/347.4

450/450

20

62/56

371.8/359.4

450/450

30

88.0/80

323.4/315.4

400/400

10

34/30

356.8/345.4

450/450

15

48/44

371.8/359.4

450/450

20

62/56

385.0/371.4

450/450

40

114.4/104

351.5/339.4

450/400

10

34/30

384.9/369.8

450/450

15

48/44

399.9/383.4

500/450

20

62/56

412.6/395.4

500/500

460

414-508

50.6

253

34.6

173

13.2

15

21.0

132.1

175

10

15.2

147.3

175

15

22.0

154.1

200

20

28.0

160.1

200

20

27.0

138.1

175

10

15.2

153.3

200

15

22.0

160.1

200

20

28.0

166.1

200

25

34.0

145.1

175

10

15.2

160.3

200

15

22.0

167.1

200

20

28.0

173.1

200

30

40.0

151.1

200

10

15.2

166.3

200

15

22.0

173.1

200

20

28.0

179.1

225

40

52.0

163.4

200

10

15.2

178.6

225

15

22.0

185.4

225

20

28.0

191.4

225

575

518-632

39.1

176

28.8

120

9.6

15

17.0

104.3

125

10

12.2

116.5

150

15

18.0

122.3

150

20

22.0

126.3

150

20

22.0

109.3

125

10

12.2

121.5

150

15

18.0

127.3

150

20

22.0

131.3

150

25

27.0

114.3

150

10

12.2

126.5

150

15

18.0

132.3

150

20

22.0

136.3

175

30

32.0

119.3

150

10

12.2

131.5

150

15

18.0

137.3

175

20

22.0

141.3

175

40

41.0

128.8

150

10

12.2

141.0

175

15

18.0

146.8

175

20

22.0

150.8

175

FLA

Full Load Amps

Hp

Nominal Horsepower

IFM

Indoor (Supply) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection
OFM

Outdoor (Condenser) Fan Motor