Table 1D — Physical Data (48Z6,Z8075-105) (cont)
LEGEND
BASE UNIT
48Z6,Z8075
48Z6,Z8090
48Z6,Z8105
RETURN/EXHAUST FAN
Plenum Fan, 47.13 in. (Any motor available on any unit.)
Quantity...Motor Hp
1...20
1...25
1...30
1...40
Motor Frame Size
256T
284T
286T
324T
Efficiency at Full Load (%) High/Premium
91/93.6
91.7/93.6
92.4/93.6
93/93.8
Fan Pulley Pitch Diameter (in.)
8.5
9.8
8.5
8.5
Motor Pulley Pitch Diameter (in.)
5.3
6.7
6.1
6.7
Shaft Diameter at Pulley (in.)
2
15
/
16
2
15
/
16
2
15
/
16
2
15
/
16
Resulting Fan Rpm
1104
1209
1271
1396
Maximum Allowable Rpm
1447
1447
1447
1447
FILTERS
Standard Efficiency Throwaway (Standard)
12...20 x 25 x 2
12...20 x 25 x 2
12...20 x 25 x 2
Quantity...Size (in.)
12...20 x 20 x 2
12...20 x 20 x 2
12...20 x 20 x 2
30% and 65% Pleated (Optional)
12...20 x 25 x 2
12...20 x 25 x 2
12...20 x 25 x 2
Quantity...Size (in.)
12...20 x 20 x 2
12...20 x 20 x 2
12...20 x 20 x 2
OPTIONAL ECONOMIZER FILTER
Aluminum Frame, Permanent
Quantity...Size (in.)
12...16 x 25 x 1
2...16 x 20 x 1
12...16 x 25 x 1
2...16 x 20 x 1
12...16 x 25 x 1
2...16 x 20 x 1
CV
— Constant Volume
HGBP — Hot Gas Bypass
MBtuh — Btuh in Thousands
TXV
— Thermostatic Expansion Valve
VAV
— Variable Air Volume