Supply-Fan Shipping Brackets —

Supply-fan ship-

ping brackets (4 per unit) must be removed from each corner of

the fan sled before starting unit.
UNIT SIZES 030-050

1. To remove brackets, raise fan sled by turning adjusting

bolt counterclockwise until spring is compressed slightly.

2. Remove screws holding shipping bracket to unit cross

rail.

3. Remove shipping bracket (top of bracket is slotted so that

it will slide out).

4. After removing all shipping brackets, level fan sled using

the adjusting screws. On all 4 corners, dimension from

cross rail to fan sled should be as shown in Fig. 50.

UNIT SIZES 055-070 — To remove shipping brackets, re-

move the 6 screws holding each bracket to the cross rail. There

are 8 brackets per unit. See Fig. 51.

After removing all shipping brackets, level fan sled using

the adjusting screws. On all 4 corners dimension from cross

rail to fan sled should be as shown in Fig. 51.
UNIT SIZES 075-105 — Supply-fan shipping brackets must

be removed from each corner of the fan sled before starting

unit. To remove shipping brackets, remove the 6 screws hold-

ing each bracket to the cross rail. There are 4 brackets per unit.

See Fig. 52.

After removing all shipping brackets, level fan sled using

the adjusting screws. On all 4 corners dimension from cross

rail to fan sled should be as shown in Fig. 52.

Return/Exhaust-Fan Shipping Brackets (48Z6,
Z8 Units) —

Return/exhaust fan shipping brackets must be

removed from each corner of the fan sled before starting unit.

To remove shipping brackets, remove 2 screws holding

each bracket to the cross rail. There are 4 brackets per unit.

After removing all shipping brackets, level the fan using the

adjustment screws. On all 4 corners the dimension from cross

rail to fan sled should be as shown in Fig. 53.

FS

BP

OACFM

TRANSDUCER

DP

RF

CFM

PP
SS

Fig. 49 — Auxiliary Control Box Details

(Size 075-105 Units with Return Fan)

LEGEND

BP — Building Pressure

Transducer

OACFM — Outdoor Air Cfm

Sensor Transducer

DP — Duct Pressure

Transducer

PPSS

Plenum Pressure

Safety Switch

FS — Filter Switch

RFCFM — Return Fan Cfm Sensor Transducer

Fig. 50 — Shipping Brackets; Size 030-050 Units

Fig. 51 — Shipping Brackets;

Size 055-070 Units

Advertising
This manual is related to the following products: