Carrier WEATHERMASTER 48ZT User Manual
Page 42
42
Table 9 — Electrical Data, 48ZG,ZN040 Units
LEGEND
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
EXHAUST
FAN
POWER SUPPLY
No. 1
No. 2
RLA
LRA
RLA
LRA
Qty
Total
FLA
Hp
FLA
Total
Hp
Total
FLA
MCA
MOCP
208/230
187-254
69.2
345
69.2
345
3
6.6
(ea)
7
1
/
2
24.2/22.0
—
—/—
199.7/197.5
250/250
6
21.2/19.2
220.9/216.7
250/250
10
33.4/30.4
233.1/227.9
300/250
15
48.4/44.0
248.1/241.5
300/300
20
61.6/56.0
261.3/253.5
300/300
10
30.8/28.0
—
—/—
206.3/203.5
250/250
6
21.2/19.2
227.5/222.7
250/250
10
33.4/30.4
239.7/233.9
300/300
15
48.4/44.0
254.7/247.5
300/300
20
62.0/56.0
267.9/259.5
300/300
15
46.2/42.0
—
—/—
221.7/217.5
250/250
6
21.2/19.2
242.9/236.7
300/300
10
33.4/30.4
255.1/247.9
300/300
15
48.4/44.0
270.1/261.5
300/300
20
62.0/56.0
283.3/273.5
350/300
20
59.4/54.0
—
—/—
234.9/229.5
300/250
6
21.2/19.2
256.1/248.7
300/300
10
33.4/30.4
268.3/259.9
300/300
15
48.4/44.0
283.3/273.5
350/300
20
62.0/56.0
296.5/285.5
350/350
25
74.8/68.0
—
—/—
251.7/243.5
300/300
6
21.2/19.2
272.9/262.7
300/300
10
33.4/30.4
285.1/273.9
350/300
15
48.4/44.0
300.1/287.5
350/350
20
62.0/56.0
313.3/299.5
350/350
460
414-508
34.6
173
34.6
173
3
3.3
(ea)
7
1
/
2
11.0
—
—
98.8
125
6
9.6
108.4
125
10
15.2
114.0
125
15
22.0
120.8
150
20
28.0
126.8
150
10
14.0
—
—
101.8
125
6
9.6
111.4
125
10
15.2
117.0
150
15
22.0
123.8
150
20
28.0
129.8
150
15
21.0
—
—
108.8
125
6
9.6
118.4
150
10
15.2
124.0
150
15
22.0
130.8
150
20
28.0
136.8
150
20
27.0
—
—
114.8
125
6
9.6
124.4
150
10
15.2
130.0
150
15
22.0
138.8
150
20
28.0
142.8
175
25
34.0
—
—
121.8
150
6
9.6
131.4
150
10
15.2
137.0
150
15
22.0
143.8
175
20
28.0
149.8
175
30
40.0
—
—
129.1
150
6
9.6
138.7
175
10
15.2
144.3
175
15
22.0
151.1
175
20
28.0
157.1
175
575
518-632
26.7
120
26.7
120
3
2.4
(ea)
7
1
/
2
9.0
—
—
76.3
100
6
7.8
84.1
110
10
12.2
88.5
100
15
18.0
94.3
110
20
22.0
98.3
110
10
11.0
—
—
78.3
100
6
7.8
86.1
110
10
12.2
90.5
110
15
18.0
96.3
110
20
22.0
100.3
125
15
17.0
—
—
84.3
110
6
7.8
92.1
110
10
12.2
96.5
110
15
18.0
102.3
125
20
22.0
106.3
125
20
22.0
—
—
89.3
110
6
7.8
97.1
110
10
12.2
101.5
125
15
18.0
107.3
125
20
22.0
101.3
125
25
27.0
—
—
94.4
110
6
7.8
102.2
125
10
12.2
106.6
125
15
18.0
112.4
125
20
22.0
116.4
125
FLA
— Full Load Amps
Hp
— Nominal Horsepower
IFM
— Indoor (Supply) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps (for wire sizing)
MOCP — Maximum Overcurrent Protection
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps