Table 19 — SGC Thermistor Designations

SGC — Staged Gas Controller

Install Unit Accessories —

For applications requiring

accessories, the following packages are available:
All units:

• barometric relief

• space temperature sensor

• CO

2

sensor

• space temperature sensor with CO

2

• airflow switch

• filter switch

• smoke detector
All 48ZG,ZT,Z6 units:

• modulating power exhaust

• pressure operated unloaders
All 48ZN,ZW,Z8 units:

• modulating power exhaust

• VFD remote display

Refer to the individual accessory installation instructions in

each accessory package for information on installing accessories.

CONTROLS INSTALLATION

Constant Volume (CV) Units —

The 48ZG,ZT,Z6 units

may be used in applications with additional control features,

options, or accessories. Refer to the appropriate accessory

installation instructions for more information on installing that

accessory. Control options and accessories available for CV

units are:
• thermostats

• enthalpy sensor

• enthalpy switch

• relative humidity sensor

• CEM (controls expansion module)

• Navigator™ hand-held display
CONTROL WIRING — The unit can be controlled with a

Carrier-approved accessory electro-mechanical or electronic

thermostat that has two stages of cooling, two stages of heating

control, and an output for fan control. The thermostat may also

include time of day scheduling or use scheduling routines built

into the ComfortLink™ controls.

Install the thermostat according to the installation instruc-

tions shipped with the accessory thermostat. Locate thermostat

assembly on a solid interior wall to sense average temperature.

Route thermostat cable or equivalent leads of colored wire

from subbase terminals through conduit into the low voltage

connections in the main control box. For thermostat TB203

connections, see Fig. 67.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American

Wire Gage) insulated wire (35 C minimum). For over 75 ft, use

no. 14 AWG insulated wire (35 C minimum). All wire larger

than no. 18 AWG cannot be directly connected at the thermostat

and will require a junction box and splice at the thermostat.

Variable Air Volume (VAV) Units —

The 48ZN,

ZW, Z8 units may be used in applications with additional con-

trol features, options, or accessories. Refer to the appropriate

accessory installation instructions for more information on in-

stalling that accessory. Refer to the Controls and Troubleshoot-

ing manual for more information concerning installation and

configuration of options and accessories. Control options and

accessories available for VAV units are:
• enthalpy sensor

• enthalpy switch

• relative humidity sensor

• CEM (controls expansion module)

• Navigator hand-held display

• VFD remote display
VAV CONTROL WIRING — The recommended types of

control wiring are shown below:

SENSORS — Sensors should be wired using single twisted

pairs of 20 AWG (American Wire Gage) conductor cable rated

for the application, except for the T-56 accessory sensor which

requires 3-conductor cable.
NOTE: Humidity and CO

2

sensors must be powered from

isolated 24-v power supplies.
HUMIDITY CONTROL AND HOT WATER AND

STEAM VALVES — These devices require 20 AWG twisted

pair conductor cables rated for the application for the 4 to

20 mA signal.
SPACE TEMPERATURE SENSOR (T-55) — The space tem-

perature sensor (P/N 33ZCT55SPT) is shipped standard with

every unit, and is located in the main control box. Space tem-

perature sensor wires are to be connected to terminals in the

unit main control box.

To connect the space temperature sensor, see Fig. 68.

THERMISTOR

PIN

CONNECTION

POINT

FUNCTION AND LOCATION

PART NO.

Thermistors

SAT1

J8 – 1,2 (SGC)

Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)

HH79NZ033

SAT2

J8 – 3,4 (SGC)

Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)

SAT3

J8 – 5,6 (SGC)

Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)

LIMTTEMP

J8 – 15,16 (SGC)

Limit Switch Thermistor (LIMTTEMP) — Inserted next the
lower limit switch (factory-installed)

MANUFACTURER

PART NO.

Regular Wiring

Plenum Wiring

Alpha

1895

American

A21451

A48301

Belden

8205

884421

Columbia

D6451

Manhattan

M13402

M64430

Quabik

6130

CAUTION

Jumper MUST be in place between pins 1 and 3, 3 and 4

or inaccurate readings could result.