Carrier WEATHERMASTER 48ZT User Manual

Page 46

Advertising
background image

46

Table 13 — Electrical Data, 48ZG,ZN070 Units

LEGEND

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan
motors rated at 0.3 FLA each.

NOMINAL

VOLTAGE

(3 Ph 60 Hz)

VOLTAGE

RANGE

COMPR

NO. 1

COMPR

NO. 2

OFM

IFM

BASE UNIT

ONLY

EXHAUST

FAN

BASE UNIT WITH

EXHAUST FAN

RLA

LRA

RLA

LRA

Total

FLA

Hp

FLA

MCA

MOCP

Total

Hp

Total

FLA

MCA

MOCP

208/230

187-254

108

506

142

690

33.0

15

46.2/42

364.8/360.6

500/500

10

34/30

398.2/390.6

500/500

15

48/44

413.2/404.6

500/500

20

62/56

426.4/416.6

500/500

20

59.4/54

378.0/372.6

500/500

10

34/30

411.4/402.6

500/500

15

48/44

426.4/416.6

500/500

20

62/56

439.6/428.6

500/500

25

74.8/68

393.4/386.6

500/500

10

34/30

426.8/416.6

500/500

15

48/44

441.8/430.6

500/500

20

62/56

455.0/442.6

500/500

30

88.0/80

406.6/389.6

500/500

10

34/30

440.0/428.6

500/500

15

48/44

455.0/442.6

500/500

20

62/56

468.2/454.6

600/500

40

114.4/104.0

433.0/422.6

500/500

10

34/30

466.4/453.0

600/500

15

48/44

481.4/466.6

600/600

20

62/56

494.1/478.6

600/600

460

414-508

50.6

253

65.4

345

16.5

15

21.0

169.9

225

10

15.2

185.1

250

15

22.0

191.9

250

20

28.0

197.9

250

20

27.0

175.9

225

10

15.2

191.1

250

15

22.0

197.9

250

20

28.0

203.9

250

25

34.0

182.9

225

10

15.2

198.1

250

15

22.0

204.9

250

20

28.0

210.9

275

30

40.0

188.9

250

10

15.2

204.1

250

15

22.0

210.9

275

20

28.0

216.9

275

40

52.0

200.9

250

10

15.2

216.1

250

15

22.0

222.9

250

20

28.0

228.9

250

575

518-632

39.1

176

52.6

276

12.0

15

17.0

133.9

175

10

12.2

146.1

175

15

18.0

151.9

200

20

22.0

155.9

200

20

22.0

138.9

175

10

12.2

151.1

200

15

18.0

156.9

200

20

22.0

160.9

200

25

27.0

143.9

175

10

12.2

156.1

200

15

18.0

161.9

200

20

22.0

165.9

200

30

32.0

148.9

200

10

12.2

161.1

200

15

18.0

166.9

200

20

22.0

170.9

200

40

41.0

157.9

200

10

12.2

170.1

200

15

18.0

175.9

225

20

22.0

179.9

225

FLA

Full Load Amps

Hp

Nominal Horsepower

IFM

Indoor (Supply) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection
OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

Advertising
This manual is related to the following products: