Carrier WEATHERMASTER 48ZT User Manual

Page 60

Advertising
background image

60

SPACE TEMPERATURE SENSOR (T-56) — The space tem-

perature sensor (P/N 33ZCT56SPT) wires are connected to

terminals in the unit main control box.

To connect the space temperature sensor, see Fig. 68.
COMMUNICATING SPACE TEMPERATURE SENSOR

(T-58) — The communicating space temperature sensor (P/N

33ZCT58SPT) is wired to the Carrier Comfort Network

®

(CCN) connections on TB202.
SPACE TEMPERATURE AVERAGING — Applications that

require averaging using multiple space temperature sensors can

be satisfied using either 4 or 9 sensors as shown in Fig. 69.
NOTE: Only Carrier sensors may be used for standard T-55

space averaging. Sensors must be used in multiples of 1, 4, and

9 only, with total sensors wiring not to exceed 1000 ft. How-

ever, space temperature reset can be accomplished with only

one sensor.
NOTE: Do not use T-56 sensors for space temperature averag-

ing because the 5-degree offset function will not work in a

multiple sensor application.
HEAT INTERLOCK RELAY (VAV Units Only — Not Neces-

sary For Digital Air Volume Applications) — Variable air vol-

ume (VAV) units using optimal start (morning warm-up) and/

or occupied heating require that room terminals be controlled

to the fully open position when the unit goes into Heating

mode. The HIR (heat interlock relay) function is provided for

this control. When the unit goes into Heating mode, the HIR is

energized to provide switch closure or opening (depending on

how the field-supplied power source is set up) to open the room

terminals. The field connections for the HIR are at TB201 ter-

minals 7 and 8. See Fig. 70.

Option and Accessory Control Wiring —

The Z

Series units may be used in applications with additional control

features, options, or accessories. Refer to the Controls and

Troubleshooting manual for more information concerning

installation and configuration of options and accessories.

Figures 70-80 contain wiring information on the following

features:
• heat interlock relay (Fig. 70)

• outdoor air enthalpy switch (Fig. 71)

• CO

2

space sensor (Fig. 72)

• filter status switch (Fig. 73)

• fan status switch (Fig. 74)

• space humidity sensor (Fig. 75)

• return air humidity sensor (Fig. 75)

• return air CO

2

sensor (Fig. 76)

• return air smoke detector (Fig. 77)

• smoke control — fire shutdown (Fig. 78)

• smoke control — purge (Fig. 79)

• smoke control — evacuation (Fig. 79)

• smoke control — pressurization (Fig. 79)

• CCN connections (Fig. 80)

Carrier Comfort Network (CCN) Interface —

The

48ZN,ZW,Z8 units can be connected to the CCN system if de-

sired. The communication bus wiring is supplied and installed

in the field. It consists of shielded, 3-conductor cable with shield

wire.

The system elements are connected to the communication

bus in a daisy chain arrangement. The positive pin of each

system element communication connector must be wired to the

positive pins of the system element on either side of it, the

negative pins must be wired to the negative pins, and the signal

pins must be wired to signal ground pins. Wiring connections

for the CCN system should be made at the terminal block using

the screw terminals. The board also contains an RJ14 CCN

plug that can be used to connect a Navigator™ device or field

service computer. There is also another RJ14 LEN (Local

Equipment Network) connection that is used to download soft-

ware. Consult CCN Contractor’s Manual for further

information.
NOTE: Conductors and drain wire must be 20 AWG minimum

stranded, tinned copper. Individual conductors must be insu-

lated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An

aluminum/polyester 100% foil shield and an outer jacket of

PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum

operating temperature range of –4 to 140 F (–20 C to 60 C) is

required. See Table 20 for cables that meet the requirements.

Table 20 — CCN Connection Approved

Shielded Cables

The following color code is recommended:

NOTE: If a cable with a different color scheme is selected, a

similar color code should be adopted for the entire network.

At each system element, the shields of its communication

bus cables must be tied together. If the communication bus is

entirely within one building, the resulting continuous field

must be connected to a ground at one point only. If the commu-

nication bus cable exits from one building and enters another,

the shields must be connected to grounds at the lightning

suppressor in each building where the cable enters or exits the

building (one point per building only).
To connect the unit to the network (Fig. 80):

1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white

(ground) and black (–) conductors. (If a different network

color scheme is used, substitute appropriate colors.)

3. Wire the CCN to the screw terminals on the COMM

board as follows (Fig. 80):

a. Secure the red (+) wire to CCN screw terminal +

on the COMM board.

b. Secure the white (ground) wire to CCN screw

terminal C on the COMM board.

c. Secure the black (–) wire to CCN screw terminal –

on the COMM board.

CAUTION

Jumper MUST be in place between pins 1 and 3, 3 and 4

or inaccurate readings could result.

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

IMPORTANT: When connecting the CCN communica-

tion bus to a system element, use a color coding system for

the entire network to simplify installation and checkout.

SIGNAL

TYPE

CCN BUS CONDUCTOR

INSULATION COLOR

COMM1 PLUG

PIN NO.

+

RED

1

GROUND

WHITE

2

BLACK

3

Advertising
This manual is related to the following products: