Smoke control modes – Carrier WEATHERMASTER 48ZT User Manual

Page 61

Advertising
background image

61

d. Secure shield wire to CCN screw terminal

SHIELD on the COMM board.

RJ14 PLUG WIRING — Units on the CCN can be monitored

from the space at the sensor through the RJ14 connector, if

desired. To wire the RJ14 connector into the CCN (Fig. 80):

1. Cut the CCN wire and strip ends of the red (+), white

(ground), and black (–) conductors. (If another wire color

scheme is used, strip ends of appropriate wires.)

2. Secure the red (+) wire to CCN screw terminal + on the

COMM board.

3. Secure the white (ground) wire to CCN screw terminal C

on the COMM board.

4. Secure the black (–) wire to CCN screw terminal – on the

COMM board.

5. Secure shield wire to CCN screw terminal SHIELD on

the COMM board.

6. Connect the other end of the communication bus cable to

the CCN communication bus.

Smoke Control Modes —

Rooftop units can be used

for aid in building smoke control in the event of a building fire.

The available functions include: Fire Shutdown, Pressuriza-

tion, Evacuation, and Smoke Purge. These functions are

enhanced when multiple rooftop units are used to zone a build-

ing. See Table 21 and Fig. 78 and 79.
FIRE SHUTDOWN — Fire Shutdown mode terminates all

unit operation (cooling, heating, supply fan, and power

exhaust). This mode prevents recirculation of contaminated air

back into the space. The mode will not allow admission into

the space of unsuitable outside air. See Fig. 78 for wiring.
PRESSURIZATION — Pressurization mode is intended to

keep smoke out of a zone. The factory-installed optional econ-

omizer is required for this function. Pressurization is accom-

plished by the following:
• opening the economizer (option)

• running the supply fan (optional inlet guide vanes open

or optional VFD at normal duct static pressure set point)

• closing the power exhaust dampers (if installed as option

or accessory)

• shutting off the power exhaust fans (if installed as option

or accessory)
This allows the space to be overpressurized relative to adja-

cent zones and prevents or slows entry of smoke into this space

from adjacent zones. See Fig. 79 for wiring.
EVACUATION — Evacuation mode removes smoke or un-

desirable air from interior spaces without reintroducing unsuit-

able air. The factory-installed optional economizer with option/

accessory power exhaust is required for this function. Evacua-

tion is accomplished by the following:
• turning the supply fan off

• opening the economizer (option required)

• running the exhaust fans (option or accessory required)

• opening the exhaust dampers.

See Fig. 79 for wiring.

SMOKE PURGE — Smoke Purge mode removes smoke

from the interior spaces and replaces it with fresh outside air.

The factory-installed optional economizer with option/

accessory power exhaust are required for this function. Smoke

purge is accomplished by the following:
• turning supply fan on

• opening the economizer (option required)

• running the exhaust fans (option or accessory required)

• opening the exhaust dampers

See Fig. 79 for wiring.

SMOKE CONTROL INSTALLATION — Implementation of

the various smoke control modes on these units requires the in-

staller to modify the unit wiring to add contacts (via either

manual switches or relays) that will selectively interrupt and

override standard factory control sequences. See Table 21 and

Fig. 78 and 79 for more information.

Table 21 — Smoke Control Modes

LEGEND

*Power exhaust option required for this mode.

†Applicable to VAV and PIC units with appropriate options.

IMPORTANT: A shorted CCN bus cable will prevent

some routines from running and may prevent unit from

starting. If abnormal conditions occur, unplug the connec-

tor. If conditions return to normal, check CCN connector,

and run new cable if necessary. A short in one section of

the bus can cause problems with all system elements on

the bus.

IMPORTANT: The cable selected for the RJ14 connector

wiring MUST be identical to the CCN communication bus

wire used for the entire network.

FUNCTION

MODE

Fire

Shutdown

Pressur-

ization

Evacuation*

Smoke
Purge*

Supply Fan

Off

On

Off

On

IGV/VFD†

Open/On

Open/On

Economizer

Closed

Open

Open

Open

Return Air
Damper

Open

Closed

Closed

Closed

Exhaust
Fans

Off

Off

On

On

Exhaust
Damper

Closed

Closed

Open

Open

IGV

Inlet Guide Vane

PIC

Product Integrated Control

VAV

Variable Air Volume

VFD

Variable Frequency Drive

T1

T2

1

2

4

3

5

6

7

8

9

10

12

13

14

15

16

TH

C

SN

T56- SPT

T55- SPT

UNIT
TB202

11

R

Y1

Y2

W1

W2

G

R

Y1

Y2

W1

W2

G

FIELD SUPPLIED THERMOSTAT

RC

1

6

5

4

3

2

TB203

Fig. 67 — Field Control Thermostat Wiring

Fig. 68 — T55 or T56 Wiring