CUTMASTER A40, A60

INTRODUCTION Manual 0-5120

2-4

2.05 Input Wiring Specifications

CutMaster A40 Power Supply Input Cable Wiring Requirements

Input voltage

Freq

Power Input

Suggested Sizes

Volts

Hz

kVA

I

1

max

I

1

eff

Fuse (amps)

Flexible Cord

(Min. mm2)

3 Phase

380

50/60

10.3

16

11

20

2.5

400

50/60

10.8

16

11

20

2.5

Line Voltages with Suggested Circuit Protection and Wire Sizes

Based on National Electric Code and Canadian Electric Code

CutMaster A60 Power Supply Input Cable Wiring Requirements

Input voltage

Freq

Power Input

Suggested Sizes

Volts

Hz

kVA

I

1

max

I

1

eff

Fuse (amps)

Flexible Cord

(Min. mm2)

3 Phase

380

50/60

11

17

11

20

2.5

400

50/60

11.5

17

11

20

2.5

Line Voltages with Suggested Circuit Protection and Wire Sizes

Based on National Electric Code and Canadian Electric Code

NOTE

Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installa-

tions refer to local or national codes.
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should

be used to minimize damage to Plasma Cutting, Welding or power distribution equipment.