02 routine service and calibration requirements, Routine service and calibration requirements -2, Fabricator 181i – Tweco 181i Thermal Arc Fabricator User Manual

Page 84

Advertising
background image

Fabricator 181i

Trouble ShooTing and Service

5-2

Manual 0-5191

FAuLT

CAuSE

rEMEDY

8 gas flow continues after

the torch trigger switch has

been released (Mig mode).

gas valve has jammed open

due to impurities in the gas or

the gas line.

have an accredited Thermal arc

service provider repair or replace

gas valve.

9 Power indicator will not

illuminate and welding arc

cannot be established.

The electricity Supply voltage

has exceeded voltage limits of

the Power Source.

ensure that the electricity Supply

voltage is within 208-265 vac.

10 Tig electrode melts when

arc is struck.

Tig Torch is connected to the

(+) ve terminal.

connect the Tig Torch to the (-) ve

terminal.

11 arc flutters during Tig

welding.

Tungsten electrode is too large

for the welding current.

Select the correct size of tungsten

electrode. refer to Table 4-7.

Table 5-1

5.02 routine Service and Calibration requirements

wArNING

There are extremely dangerous voltage and power levels present inside this Power Source. do not

attempt to open or repair unless you are an accredited Thermal arc Service Provider. disconnect the

Welding Power Source from the electricity Supply voltage before disassembling.

routine Inspection, Testing & Maintenance
The inspection and testing of the Power Source and associated accessories shall be carried out in accordance

with Section 5 of en 60974-1: Safety in Welding and allied Processes-Part 2 electrical. This includes an insulation

resistance test and an earthing test to ensure the integrity of the Power Source is compliant with Thermal arc's

original specifications.
if equipment is to be used in a hazardous location or environments with a high risk of electrocution as outlined in

en 60974-1, then the above tests should be carried out prior to entering this location.

A. Testing Schedule

1. For transportable equipment, at least once every 3 months; and
2. For fixed equipment, at least once every 12 months.

The owners of the equipment shall keep a suitable record of the periodic tests and a system of tagging, includ-

ing the date of the most recent inspection.

a transportable Power Source is deemed to be any equipment that is not permanently connected and fixed in

the position in which it is operated.

NOTE

Please refer to local guidelines for further information.

B. Insulation resistance

Minimum insulation resistance for in-service Thermal arc Power Sources shall be measured at a voltage of

500v between the parts referred to in Table 6-1below. Power Sources that do not meet the insulation resis-

tance requirements set out below shall be withdrawn from service and not returned until repairs have been

performed such that the requirements outlined below are met.

Advertising