Pump installation – Viking Pump TSM420: HL-LL 4925 User Manual

Page 3

Advertising
background image

SECTION TSM 420

ISSUE

E

PAGE 3 OF 18

fIgURE 2

4. PUMP SPEED - The slower the operating speed the

longer the longer the service life This is particularly true

on refrigeration ammonia pumps where:
4.1. the liquid has virtually no lubrication value or film

strength to prevent surface to surface contact and,
4.2. the heat generated by friction can cause the ammonia

to vaporize, which in turn causes cavitation

5. TESTING - All Viking Ammonia pumps are tested prior

to shipment, but it is good practice to pressure test the

pump along with the rest of the system before adding

the ammonia Shipping, storage and installation all have

strange ways of producing detrimental effects on sound

equipment

6. SYSTEM CLEANLINESS - Ammonia is a good

detergent, as such it has a tendency to remove all

the dirt, pipe scale, weld beads, and loose or foreign

material in the system Unfortunately not all of this

material settles out in traps or can be caught in strainers;

and as a result, a considerable amount goes through the

pump, the abrasive solids going through the pump will

of course cause excessive wear during the start up of

a new system, thus the cleaner a new system is before

start up, the less wear and trouble with the pump

7. STAND BY EQUIPMENT - Stand by equipment is always

good insurance when possible breakdown of any single

piece of equipment could be jeopardise the operation of

the entire system Often on circulating, two pumps are

used, with operation of the pumps alternated by day or

week Alternating operation of the pumps is not always

considered the best practice since both pumps may both

wear out at the same time If operation of the pumps

is not alternated, the stand by pump should be run for

several hours at least once a month to make sure it is in

good operating condition Sometimes on large systems

three pumps are used, two running continuously, with

the third for use as a standby and for peak loads

One of the most important considerations on any circulation

Refrigeration Ammonia pump installation is proper design of

the pump inlet line Refrigeration Ammonia, when stored in

a closed container, will exert a pressure within the container

equal to its saturated vapor pressure The saturated pressure

of a liquid may be defined as the pressure at which both liquid

and vapor exist in equilibrium in the same container The

vapor pressure has a different value for each temperature

The saturated vapor pressure of water at 212ºF (waters

boiling point) is 14 7 PSIA In other words, when handling

Refrigeration Ammonia, we are handling a liquid, which is at its

boiling point A slight reduction in the pressure being exerted

on the liquid will cause boiling and thus vapor formation
With this information in mind let us examine figure 2, which

illustrates one of the most important considerations when

installing a pump to handle Refrigeration Ammonia
The pressure (P1) in the accumulator is equal to the

saturated vapor pressure of the ammonia When the pump

is not running the pressure (P2) at the pump inlet is equal to

the tank pressure (P1) plus the static head (H) P2 = P1 + H

As soon as the pump started and the liquid begins to flow, the

pressure at the pump (P2) will drop by an amount equal to

the pressure loss in the piping between the accumulator and

the pump When liquid is flowing: P2 = P1 + H - (pressure

loss in the piping)
In order to have an installation in which the pump handles all

liquid and no vapor, the pressure drop in the piping must be

equal to or less than the static head (H) on the pump inlet If the

piping loss is greater than the static head, the liquid ammonia

will start to boil or vaporize and the pump will be required to

take in a mixture of liquid and vapor Since a given weight of

vapor takes up a much greater volume than the same weight

of liquid, handling both liquid and vapor will reduce the liquid

output from the pump The vapor is compressed back to a

liquid on the discharge side of the pump causing it to be noisy

and to wear rapidly
Values for pipe friction losses for calculating suction line

pressure drop can be found in refrigeration hand books
Since Viking pumps are of the positive displacement type, be

sure that there is no obstruction in the discharge line and that

all valves are in operating position before starting the pump

Factory assembled port will have right hand port suction and

top port discharge unless otherwise specified Port location

is determined by looking at shaft end of pump The pressure

relief valve on the pump provides over pressure protection

Return-to-Tank pressure relief valves should be mounted on

the discharge side of the pump Internal type pressure relief

valves should be mounted with the cap pointing towards the

suction side of pump Also see formation under

Relief Valve

Instructions page 12. The Viking pump mounted return-to-

tank pressure relief valve

(see figure 16, PAgE 11 & figure

17, page 12) is fitted with a pressure relief plug to keep a

valid off return line from building up excessive pressures

PUMP INSTALLATION

ACCUMULATOR

PUMP

Advertising