Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER
SUPPLY

VOLTS−PH−HZ

VOLTAGE

RANGE

COMPRESSOR

(EA)

OFM

FLA

IFM
FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

05

(cont)

208/230-3-60

(cont)

187

253

14.6

91

0.9

4.9

1.4

Low

Ċ

Ċ

Ċ/Ċ

25.4/25.4

30/30

Ċ

25/25

106/106

Ċ

208A00

10.0/11.5

3.8/ 5.0

25.4/25.4

30/30

030A00

25/25

106/106

15

209A00

15.0/17.3

5.6/ 7.5

26.6/29.5

30/30

030A00

25/27

106/106

15

210A00

20.0/23.1

7.5/10.0

32.9/36.7

40/40

030A00

30/34

106/106

15

211A00

30.0/34.6

11.3/15.0

45.4/51.2

50/60

030A00

42/47

106/106

15

212A00

40.0/46.2

15.0/20.0

57.9/65.6

60/70

031A00

53/60

106/106

16

5.2

High

Ċ

Ċ

Ċ/Ċ

25.7/25.7

30/30

Ċ

25/25

125/125

Ċ

208A00

10.0/11.5

3.8/ 5.0

25.7/25.7

30/30

030A00

25/25

125/125

15

209A00

15.0/17.3

5.6/ 7.5

27.0/29.9

30/30

030A00

25/28

125/125

15

210A00

20.0/23.1

7.5/10.0

33.3/37.1

40/40

030A00

31/34

125/125

15

211A00

30.0/34.6

11.3/15.0

45.8/51.6

50/60

030A00

42/47

125/125

15

212A00

40.0/46.2

15.0/20.0

58.3/66.0

60/70

031A00

54/61

125/125

16

460-3-60

414

506

7.1

46

0.5

2.1

Ċ

Low

Ċ

Ċ

Ċ

11.4

15

Ċ

11

53

Ċ

215A00

5.8

5.0

11.4

15

030A00

11

53

15

216A00

8.7

7.5

13.5

15

030A00

12

53

15

217A00

11.5

10.0

17.1

20

030A00

16

53

15

218A00

17.3

15.0

24.3

25

030A00

22

53

15

219A00

23.1

20.0

31.5

35

030A00

29

53

15

2.6

High

Ċ

Ċ

Ċ

11.9

15

Ċ

12

62

Ċ

215A00

5.8

5.0

11.9

15

030A00

12

62

15

216A00

8.7

7.5

14.1

15

030A00

13

62

15

217A00

11.5

10.0

17.7

20

030A00

16

62

15

218A00

17.3

15.0

24.9

25

030A00

23

62

15

219A00

23.1

20.0

32.1

35

030A00

30

62

15

2.1

0.6

Low

Ċ

Ċ

Ċ

12.0

15

Ċ

12

54

Ċ

215A00

5.8

5.0

12.0

15

030A00

12

54

15

216A00

8.7

7.5

14.2

15

030A00

13

54

15

217A00

11.5

10.0

17.8

20

030A00

16

54

15

218A00

17.3

15.0

25.0

30

030A00

23

54

15

219A00

23.1

20.0

32.2

35

030A00

30

54

15

2.6

High

Ċ

Ċ

Ċ

12.5

15

Ċ

12

63

Ċ

215A00

5.8

5.0

12.5

15

030A00

12

63

15

216A00

8.7

7.5

14.8

15

030A00

14

63

15

217A00

11.5

10.0

18.4

20

030A00

17

63

15

218A00

17.3

15.0

25.7

30

030A00

24

63

15

219A00

23.1

20.0

32.9

35

030A00

30

63

15

575-3-60

518

632

5.0

34.0

0.4

2.0

Ċ

Low

Ċ

Ċ

Ċ

9.0

15

Ċ

9

40

Ċ

221A00

9.2

10.0

14.1

15

030A00

13

40

15

222A00

13.9

15.0

20.0

25

030A00

18

40

15

223A00

18.5

20.0

25.8

30

030A00

24

40

15

High

Ċ

Ċ

Ċ

8.9

15

Ċ

9

46

Ċ

221A00

9.2

10.0

14.0

15

030A00

13

46

15

222A00

13.9

15.0

19.9

20

030A00

18

46

15

223A00

18.5

20.0

25.6

30

030A00

24

46

15

1.4

Low

Ċ

Ċ

Ċ

10.4

15

Ċ

10

42

Ċ

221A00

9.2

10.0

15.9

20

030A00

15

42

15

222A00

13.9

15.0

21.8

25

030A00

20

42

15

223A00

18.5

20.0

27.5

30

030A00

25

42

15

High

Ċ

Ċ

Ċ

10.3

15

Ċ

10

48

Ċ

221A00

9.2

10.0

15.8

20

030A00

14

48

15

222A00

13.9

15.0

21.6

25

030A00

20

48

15

223A00

18.5

20.0

27.4

30

030A00

25

48

15

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16