Carrier 50PG03-16 User Manual

Page 16

Advertising
background image

16

Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER

SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

(EA.)

OFM

FLA

IFM

FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE
PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

08

(cont)

575-3-60

(cont)

518

632

6.4

30.0

0.8

2.8

3.0

Low

Ċ

Ċ

Ċ

18.1

20

Ċ

19

86

Ċ

239A00

13.9

15.0

23.6

25

030A00

22

86

15

240A00

23.1

25.0

35.1

40

030A00

32

86

15

241A00

32.3

35.0

46.7

50

030A00

43

86

15

242A00

37.0

40.0

52.4

60

030A00

48

86

15

High

Ċ

Ċ

Ċ

18.9

25

Ċ

20

98

Ċ

239A00

13.9

15.0

24.6

25

030A00

23

98

15

240A00

23.1

25.0

36.1

40

030A00

33

98

15

241A00

32.3

35.0

47.7

50

030A00

44

98

15

242A00

37.0

40.0

53.4

60

030A00

49

98

15

09

208/230-3-60

187

253

16.0

91

1.5

5.2

Ċ

Low

Ċ

Ċ

Ċ/Ċ

44.3/ 44.3

60/ 60

Ċ

46/ 46

218/218

Ċ

225A00

20.0/23.1

7.5/10.0

44.3/ 44.3

60/ 60

030A00

46/ 46

218/218

15

226A00

30.0/34.6

11.3/15.0

44.3/ 49.8

60/ 60

030A00

46/ 46

218/218

15

227A00

50.0/57.7

18.8/25.0

69.0/ 78.7

70/ 80

031A00

64/ 72

218/218

16

228A00

70.0/80.8

26.3/35.0

94.1/107.5

100/110

031A00

87/ 99

218/218

17

229A00

80.0/92.4

30.0/40.0

106.6/122.0

110/125

031A00

98/112

218/218

17

High

Ċ

Ċ

Ċ/Ċ

49.3/ 49.3

60/ 60

Ċ

52/ 52

261/261

Ċ

225A00

20.0/23.1

7.5/10.0

49.3/ 49.3

60/ 60

030A00

52/ 52

261/261

15

226A00

30.0/34.6

11.3/15.0

50.3/ 56.1

60/ 60

030A00

52/ 52

261/261

15

227A00

50.0/57.7

18.8/25.0

75.3/ 84.9

80/ 90

031A00

69/ 78

261/261

16

228A00

70.0/80.8

26.3/35.0

100.3/113.8

110/125

031A00

92/105

261/261

17

229A00

80.0/92.4

30.0/40.0

112.8/128.2

125/150

031A00

104/118

261/261

17

3.0

Low

Ċ

Ċ

Ċ/Ċ

47.3/ 47.3

60/ 60

Ċ

50/ 50

222/222

Ċ

225A00

20.0/23.1

7.5/10.0

47.3/ 47.3

60/ 60

030A00

50/ 50

222/222

15

226A00

30.0/34.6

11.3/15.0

47.8/ 53.6

60/ 60

030A00

50/ 50

222/222

15

227A00

50.0/57.7

18.8/25.0

72.8/ 82.4

80/ 90

031A00

67/ 76

222/222

16

228A00

70.0/80.8

26.3/35.0

97.8/111.3

100/125

031A00

90/102

222/222

17

229A00

80.0/92.4

30.0/40.0

110.3/125.7

125/150

031A00

101/116

222/222

17

High

Ċ

Ċ

Ċ/Ċ

52.3/ 52.3

60/ 60

Ċ

55/ 55

265/265

Ċ

225A00

20.0/23.1

7.5/10.0

52.3/ 52.3

60/ 60

030A00

55/ 55

265/265

15

226A00

30.0/34.6

11.3/15.0

54.0/ 59.8

60/ 60

030A00

55/ 55

265/265

15

227A00

50.0/57.7

18.8/25.0

79.0/ 88.7

80/ 90

031A00

73/ 82

265/265

16

228A00

70.0/80.8

26.3/35.0

104.1/117.5

110/125

031A00

96/108

265/265

17

229A00

80.0/92.4

30.0/40.0

116.6/132.0

125/150

031A00

107/121

265/265

17

460-3-60

414

506

7.1

46

0.8

2.6

Ċ

Low

Ċ

Ċ

Ċ

20.1

25

Ċ

21

110

Ċ

232A00

11.5

10.0

20.1

25

030A00

21

110

15

233A00

17.3

15.0

24.9

25

030A00

23

110

15

234A00

28.9

25.0

39.3

40

030A00

36

110

15

235A00

40.4

35.0

53.8

60

030A00

49

110

15

236A00

46.2

40.0

61.0

70

033A00

56

110

19

4.8

High

Ċ

Ċ

Ċ

22.3

25

Ċ

24

132

Ċ

232A00

11.5

10.0

22.3

25

030A00

24

132

15

233A00

17.3

15.0

27.7

30

030A00

25

132

15

234A00

28.9

25.0

42.1

45

030A00

39

132

15

235A00

40.4

35.0

56.5

60

030A00

52

132

15

236A00

46.2

40.0

63.7

70

033A00

59

132

19

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16