Carrier 50PG03-16 User Manual

Page 14

Advertising
background image

14

Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER

SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

(EA)

OFM

FLA

IFM

FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

06

(cont)

575-3-60

518

632

6.1

40

0.8

2.0

Ċ

Low
and

High

Ċ

Ċ

Ċ

10.4

15

Ċ

10

53

Ċ

221A00

9.2

10.0

14.0

15

030A00

13

53

15

222A00

13.9

15.0

20.1

20

030A00

18

53

15

223A00

18.5

20.0

25.6

30

030A00

24

53

15

254A00

23.1

25.0

31.4

30

030A00

29

53

15

1.4

Low
and

High

Ċ

Ċ

Ċ

11.7

15

Ċ

12

54

Ċ

221A00

9.2

10.0

15.8

20

030A00

15

54

15

222A00

13.9

15.0

21.6

25

030A00

20

54

15

223A00

18.5

20.0

27.3

30

030A00

25

54

15

254A00

23.1

25.0

33.1

30

030A00

30

54

15

07

208/230-3-60

187

253

20.5

149

1.5

5.2

Ċ

Low

Ċ

Ċ

Ċ/Ċ

32.3/32.3

50/50

Ċ

31/31

182/182

Ċ

208A00

10.0/11.5

3.8/ 5.0

32.3/32.3

50/50

030A00

31/31

182/182

15

209A00

15.0/17.3

5.6/ 7.5

32.3/32.3

50/50

030A00

31/31

182/182

15

210A00

20.0/23.1

7.5/10.0

32.3/35.4

50/50

030A00

31/33

182/182

15

211A00

30.0/34.6

11.3/15.0

44.0/49.8

50/50

030A00

41/46

182/182

15

212A00

40.0/46.2

15.0/20.0

56.5/64.2

60/70

031A00

52/59

182/182

16

213A00

50.0/57.7

18.8/25.0

69.0/78.7

70/80

031A00

64/72

182/182

16

7.5

Ċ

High

Ċ

Ċ

Ċ/Ċ

34.6/34.6

50/50

Ċ

34/34

208/208

Ċ

208A00

10.0/11.5

3.8/ 5.0

34.6/34.6

50/50

030A00

34/34

208/208

15

209A00

15.0/17.3

5.6/ 7.5

34.6/34.6

50/50

030A00

34/34

208/208

15

210A00

20.0/23.1

7.5/10.0

34.6/38.2

50/50

030A00

34/35

208/208

15

211A00

30.0/34.6

11.3/15.0

46.9/52.7

50/60

030A00

43/48

208/208

15

212A00

40.0/46.2

15.0/20.0

59.4/67.1

60/70

031A00

55/62

208/208

16

213A00

50.0/57.7

18.8/25.0

71.9/81.5

80/90

031A00

66/75

208/208

16

5.2

1.4

Low

Ċ

Ċ

Ċ/Ċ

33.7/33.7

50/50

Ċ

33/33

184/184

Ċ

208A00

10.0/11.5

3.8/ 5.0

33.7/33.7

50/50

030A00

33/33

184/184

15

209A00

15.0/17.3

5.6/ 7.5

33.7/33.7

50/50

030A00

33/33

184/184

15

210A00

20.0/23.1

7.5/10.0

33.7/33.1

50/50

030A00

33/34

184/184

15

211A00

30.0/34.6

11.3/15.0

45.8/51.5

50/60

030A00

42/47

184/184

15

212A00

40.0/46.2

15.0/20.0

58.3/66.0

60/70

031A00

54/61

184/184

16

213A00

50.0/57.7

18.8/25.0

70.8/80.4

80/90

031A00

65/74

184/184

16

7.5

High

Ċ

Ċ

Ċ/Ċ

36/36

50/50

Ċ

36/36

210/210

Ċ

208A00

10.0/11.5

3.8/ 5.0

36.0/36.0

50/50

030A00

36/36

210/210

15

209A00

15.0/17.3

5.6/ 7.5

36.0/36.0

50/50

030A00

36/36

210/210

15

210A00

20.0/23.1

7.5/10.0

36.1/40.0

50/50

030A00

36/37

210/210

15

211A00

30.0/34.6

11.3/15.0

48.6/54.4

50/60

030A00

45/50

210/210

15

212A00

40.0/46.2

15.0/20.0

61.1/68.9

70/70

031A00

56/63

210/210

16

213A00

50.0/57.7

18.8/25.0

73.6/83.3

80/90

031A00

68/77

210/210

16

460-3-60

414

506

9.6

75

0.8

2.6

Ċ

Low

Ċ

Ċ

Ċ

15.4

25

Ċ

15

92

Ċ

215A00

5.8

5.0

15.4

25

030A00

15

92

15

216A00

8.7

7.5

15.4

25

030A00

15

92

15

217A00

11.5

10.0

17.7

25

030A00

16

92

15

218A00

17.3

15.0

24.9

25

030A00

23

92

15

219A00

23.1

20.0

32.1

35

030A00

30

92

15

220A00

28.9

25.0

39.3

40

030A00

36

92

15

3.4

High

Ċ

Ċ

Ċ

16.2

25

Ċ

16

105

Ċ

215A00

5.8

5.0

16.2

25

030A00

16

105

15

216A00

8.7

7.5

16.2

25

030A00

16

105

15

217A00

11.5

10.0

18.7

25

030A00

17

105

15

218A00

17.3

15.0

25.9

30

030A00

24

105

15

219A00

23.1

20.0

33.1

35

030A00

30

105

15

220A00

28.9

25.0

40.3

45

030A00

37

105

15

2.6

0.6

Low

Ċ

Ċ

Ċ

16.0

25

Ċ

16

93

Ċ

215A00

5.8

5.0

16.0

25

030A00

16

93

15

216A00

8.7

7.5

16.0

25

030A00

16

93

15

217A00

11.5

10.0

18.4

25

030A00

17

93

15

218A00

17.3

15.0

25.7

30

030A00

24

93

15

219A00

23.1

20.0

32.9

35

030A00

30

93

15

220A00

28.9

25.0

40.1

45

030A00

37

93

15

3.4

High

Ċ

Ċ

Ċ

16.8

25

Ċ

17

106

Ċ

215A00

5.8

5.0

16.8

25

030A00

17

106

15

216A00

8.7

7.5

16.8

25

030A00

17

106

15

217A00

11.5

10.0

19.4

25

030A00

18

106

15

218A00

17.3

15.0

26.7

30

030A00

25

106

15

219A00

23.1

20.0

33.9

35

030A00

31

106

15

220A00

28.9

25.0

41.1

45

030A00

38

106

15

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16