Carrier 50PG03-16 User Manual

Page 25

Advertising
background image

25

Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER
SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

IFM
FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

07

208/230-3-60

187

253

20.5

149

1.5

5.2

Ċ

Low

Ċ

Ċ

Ċ/Ċ

37.2/37.2

50/50

Ċ

37/37

187/187

Ċ

208A00

10.0/11.5

3.8/ 5.0

37.2/37.2

50/50

030A00

37/37

187/187

15

209A00

15.0/17.3

5.6/ 7.5

37.2/37.2

50/50

030A00

37/37

187/187

15

210A00

20.0/23.1

7.5/10.0

37.5/40.8

50/50

030A00

37/38

187/187

15

211A00

30.0/34.6 11.3/15.0

50.0/55.2

50/50

030A00

46/51

187/187

15

212A00

40.0/46.2 15.0/20.0

62.5/69.7

60/70

031A00

58/65

187/187

16

213A00

50.0/57.7 18.8/25.0

75.1/84.1

70/80

031A00

69/78

187/187

16

7.5

High

Ċ

Ċ

Ċ/Ċ

39.5/39.5

50/50

Ċ

39/39

213/213

Ċ

208A00

10.0/11.5

3.8/ 5.0

39.5/39.5

50/50

030A00

39/39

213/213

15

209A00

15.0/17.3

5.6/ 7.5

39.5/39.5

50/50

030A00

39/39

213/213

15

210A00

20.0/23.1

7.5/10.0

40.4/43.7

50/50

030A00

39/41

213/213

15

211A00

30.0/34.6 11.3/15.0

52.9/58.1

60/60

030A00

49/54

213/213

15

212A00

40.0/46.2 15.0/20.0

65.4/72.5

70/80

031A00

60/67

213/213

16

213A00

50.0/57.7 18.8/25.0

77.9/87.0

80/90

031A00

72/81

213/213

16

5.2

1.4

Low

Ċ

Ċ

Ċ/Ċ

38.6/38.6

50/50

Ċ

38/38

189/189

Ċ

208A00

10.0/11.5

3.8/ 5.0

38.6/38.6

50/50

030A00

38/38

189/189

15

209A00

15.0/17.3

5.6/ 7.5

38.6/38.6

50/50

030A00

38/38

189/189

15

210A00

20.0/23.1

7.5/10.0

39.3/42.6

50/50

030A00

38/40

189/189

15

211A00

30.0/34.6 11.3/15.0

51.8/57.0

60/60

030A00

48/53

189/189

15

212A00

40.0/46.2 15.0/20.0

64.3/71.4

70/80

031A00

59/66

189/189

16

213A00

50.0/57.7 18.8/25.0

76.8/85.9

80/90

031A00

71/80

189/189

16

7.5

High

Ċ

Ċ

Ċ/Ċ

40.9/40.9

60/60

Ċ

41/41

214/214

Ċ

208A00

10.0/11.5

3.8/ 5.0

40.9/40.9

60/60

030A00

41/41

214/214

15

209A00

15.0/17.3

5.6/ 7.5

40.9/40.9

60/60

030A00

41/41

214/214

15

210A00

20.0/23.1

7.5/10.0

42.2/45.4

60/60

030A00

41/42

214/214

15

211A00

30.0/34.6 11.3/15.0

54.7/59.9

60/70

031A00

50/56

214/214

15

212A00

40.0/46.2 15.0/20.0

67.2/74.3

70/80

031A00

62/69

214/214

16

213A00

50.0/57.7 18.8/25.0

79.7/88.7

80/90

031A00

73/82

214/214

16

460-3-60

414

506

9.6

75

0.8

2.6

Ċ

Low

Ċ

Ċ

Ċ

17.6

25

Ċ

17

94

Ċ

215A00

5.8

5.0

17.6

25

030A00

17

94

15

216A00

8.7

7.5

17.6

25

030A00

17

94

15

217A00

11.5

10.0

20.4

25

030A00

19

94

15

218A00

17.3

15.0

27.6

30

030A00

25

94

15

219A00

23.1

20.0

34.8

35

030A00

32

94

15

220A00

28.9

25.0

42.1

45

030A00

39

94

15

3.4

High

Ċ

Ċ

Ċ

18.4

25

Ċ

18

107

Ċ

215A00

5.8

5.0

18.4

25

030A00

18

107

15

216A00

8.7

7.5

18.4

25

030A00

18

107

15

217A00

11.5

10.0

21.4

25

030A00

20

107

15

218A00

17.3

15.0

28.6

30

030A00

26

107

15

219A00

23.1

20.0

35.8

40

030A00

33

107

15

220A00

28.9

25.0

43.1

45

030A00

40

107

15

2.6

0.6

Low

Ċ

Ċ

Ċ

18.2

25

Ċ

18

95

Ċ

215A00

5.8

5.0

18.2

25

030A00

18

95

15

216A00

8.7

7.5

18.2

25

030A00

18

95

15

217A00

11.5

10.0

21.2

25

030A00

19

95

15

218A00

17.3

15.0

28.4

30

030A00

26

95

15

219A00

23.1

20.0

35.6

40

030A00

33

95

15

220A00

28.9

25.0

42.8

45

030A00

39

95

15

3.4

High

Ċ

Ċ

Ċ

19.0

25

Ċ

19

108

Ċ

215A00

5.8

5.0

19.0

25

030A00

19

108

15

216A00

8.7

7.5

19.0

25

030A00

19

108

15

217A00

11.5

10.0

22.2

25

030A00

20

108

15

218A00

17.3

15.0

29.4

30

030A00

27

108

15

219A00

23.1

20.0

36.6

40

030A00

34

108

15

220A00

28.9

25.0

43.8

45

030A00

40

108

15

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16

Advertising