27

Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER
SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

IFM
FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

08

(cont)

575-3-60

518

632

6.4

30.0

0.8

2.0

Ċ

Low

Ċ

Ċ

Ċ

20.1

20

Ċ

21

86

Ċ

239A00

13.9

15.0

22.0

25

030A00

21

86

15

240A00

23.1

25.0

33.5

35

030A00

31

86

15

241A00

32.3

35.0

45.1

50

030A00

41

86

15

242A00

37.0

40.0

50.9

60

030A00

47

86

15

High

Ċ

Ċ

Ċ

20.6

20

Ċ

22

104

Ċ

239A00

13.9

15.0

23.0

25

030A00

22

104

15

240A00

23.1

25.0

34.5

35

030A00

32

104

15

241A00

32.3

35.0

46.1

50

030A00

42

104

15

242A00

37.0

40.0

51.9

60

030A00

48

104

15

575-3-60

518

632

6.4

30.0

0.8

2.8

3.0

Low

Ċ

Ċ

Ċ

19.9

25

Ċ

21

88

Ċ

239A00

13.9

15.0

25.7

30

030A00

24

88

15

240A00

23.1

25.0

37.3

40

030A00

34

88

15

241A00

32.3

35.0

48.8

50

030A00

45

88

15

242A00

37.0

40.0

54.6

60

030A00

50

88

15

High

Ċ

Ċ

Ċ

20.7

25

Ċ

22

100

Ċ

239A00

13.9

15.0

26.7

30

030A00

25

100

15

240A00

23.1

25.0

38.3

40

030A00

35

100

15

241A00

32.3

35.0

49.8

50

030A00

46

100

15

242A00

37.0

40.0

55.6

60

030A00

51

100

15

09

208/230-3-60

187

253

16.0

91

1.5

5.2

Ċ

Low

Ċ

Ċ

Ċ/Ċ

49.1/ 49.1

60/ 60

Ċ

52/ 52

223/223

Ċ

225A00

20.0/23.1

7.5/10.0

49.1/ 49.1

60/ 60

030A00

52/ 52

223/223

15

226A00

30.0/34.6 11.3/15.0

50.0/ 55.2

60/ 60

030A00

52/ 52

223/223

15

227A00

50.0/57.7 18.8/25.0

75.1/ 84.1

80/ 90

031A00

69/ 78

223/223

16

228A00

70.0/80.8 26.3/35.0

100.1/113.0

110/125

031A00

92/104

223/223

17

229A00

80.0/92.4 30.0/40.0

112.6/127.4

125/150

031A00

104/118

223/223

17

10.2

High

Ċ

Ċ

Ċ/Ċ

54.1/ 54.1

60/ 60

Ċ

58/ 58

266/266

Ċ

225A00

20.0/23.1

7.5/10.0

54.1/ 54.1

60/ 60

031A00

58/ 58

266/266

15

226A00

30.0/34.6 11.3/15.0

56.3/ 61.5

60/ 70

031A00

58/ 58

266/266

15

227A00

50.0/57.7 18.8/25.0

81.3/ 90.4

90/100

031A00

75/ 84

266/266

16

228A00

70.0/80.8 26.3/35.0

106.3/119.2

110/125

031A00

98/110

266/266

17

229A00

80.0/92.4 30.0/40.0

118.8/133.7

125/150

031A00

109/123

266/266

17

5.2

3.0

Low

Ċ

Ċ

Ċ/Ċ

52.1/ 52.1

60/ 60

Ċ

55/ 55

227/227

Ċ

225A00

20.0/23.1

7.5/10.0

52.1/ 52.1

60/ 60

031A00

55/ 55

227/227

15

226A00

30.0/34.6 11.3/15.0

53.8/ 59.0

60/ 60

031A00

55/ 55

227/227

15

227A00

50.0/57.7 18.8/25.0

78.8/ 87.9

80/ 90

031A00

72/ 81

227/227

16

228A00

70.0/80.8 26.3/35.0

103.8/116.7

110/125

031A00

96/108

227/227

17

229A00

80.0/92.4 30.0/40.0

116.3/131.2

125/150

031A00

107/121

227/227

17

10.2

High

Ċ

Ċ

Ċ/Ċ

57.1/ 57.1

70/ 70

Ċ

61/ 61

270/270

Ċ

225A00

20.0/23.1

7.5/10.0

57.1/ 57.1

70/ 70

030A00

61/ 61

270/270

15

226A00

30.0/34.6 11.3/15.0

60.0/ 65.2

70/ 70

030A00

61/ 61

270/270

15

227A00

50.0/57.7 18.8/25.0

85.1/ 94.1

90/100

031A00

78/ 87

270/270

16

228A00

70.0/80.8 26.3/35.0

110.1/123.0

125/125

031A00

101/114

270/270

17

229A00

80.0/92.4 30.0/40.0

122.6/137.4

125/150

031A00

113/127

270/270

17

460-3-60

414

506

7.1

46

0.8

2.6

Ċ

Low

Ċ

Ċ

Ċ

22.2

25

Ċ

24

112

Ċ

232A00

11.5

10.0

22.2

25

030A00

24

112

15

233A00

17.3

15.0

27.6

30

030A00

25

112

15

234A00

28.9

25.0

42.1

45

030A00

39

112

15

235A00

40.4

35.0

56.5

60

030A00

52

112

15

236A00

46.2

40.0

63.7

70

033A00

59

112

19

4.8

High

Ċ

Ċ

Ċ

24.4

30

Ċ

26

134

Ċ

232A00

11.5

10.0

24.4

30

030A00

26

134

15

233A00

17.3

15.0

30.4

35

030A00

28

134

15

234A00

28.9

25.0

44.8

45

030A00

41

134

15

235A00

40.4

35.0

59.2

60

030A00

54

134

15

236A00

46.2

40.0

66.5

70

033A00

61

134

19

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16