Carrier 50PG03-16 User Manual

Page 29

Advertising
background image

29

Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER
SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

IFM
FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

12

(cont)

460-3-60

(cont)

414

506

7.7

50

1.0

3.4

1.2

Low

Ċ

Ċ

Ċ

26.1

30

Ċ

28

135

Ċ

232A00

11.5

10.0

26.1

30

030A00

28

135

15

233A00

17.3

15.0

30.1

35

030A00

28

135

15

234A00

28.9

25.0

44.6

45

030A00

41

135

15

235A00

40.4

35.0

59.0

60

030A00

54

135

15

236A00

46.2

40.0

66.2

70

033A00

61

135

19

237A00

57.7

50.0

66.2

70

033A00

74

135

19

4.8

High

Ċ

Ċ

Ċ

27.5

30

Ċ

29

143

Ċ

232A00

11.5

10.0

27.5

30

030A00

29

143

15

233A00

17.3

15.0

31.9

35

030A00

29

143

15

234A00

28.9

25.0

46.3

50

030A00

43

143

15

235A00

40.4

35.0

60.7

70

033A00

56

143

15

236A00

46.2

40.0

68.0

70

033A00

63

143

19

237A00

57.7

50.0

68.0

80

033A00

76

143

19

575-3-60

518

632

6.1

40.0

0.8

2.8

Ċ

Low

Ċ

Ċ

Ċ

20.1

25

Ċ

21

124

Ċ

239A00

13.9

15.0

23.0

25

030A00

21

124

15

240A00

23.1

25.0

34.5

35

030A00

32

124

15

241A00

32.3

35.0

46.1

50

030A00

42

124

15

242A00

37.0

40.0

51.9

60

030A00

48

124

15

243A00

46.2

50.0

51.9

60

030A00

58

124

15

3.3

High

Ċ

Ċ

Ċ

20.4

25

Ċ

22

144

Ċ

239A00

13.9

15.0

23.6

25

030A00

22

144

15

240A00

23.1

25.0

35.2

35

030A00

32

144

15

241A00

32.3

35.0

46.7

50

030A00

43

144

15

242A00

37.0

40.0

52.5

60

030A00

48

144

15

243A00

46.2

50.0

52.5

60

030A00

59

144

15

2.8

3.0

Low

Ċ

Ċ

Ċ

22.8

25

Ċ

25

111

Ċ

239A00

13.9

15.0

26.7

30

030A00

25

111

15

240A00

23.1

25.0

38.3

40

030A00

35

111

15

241A00

32.3

35.0

49.8

50

030A00

46

111

15

242A00

37.0

40.0

55.6

60

030A00

51

111

15

243A00

46.2

50.0

55.6

60

030A00

62

111

15

3.3

High

Ċ

Ċ

Ċ

22.8

25

Ċ

25

111

Ċ

239A00

13.9

15.0

26.7

30

030A00

25

111

15

240A00

23.1

25.0

38.3

40

030A00

35

111

15

241A00

32.3

35.0

49.8

50

030A00

46

111

15

242A00

37.0

40.0

55.6

60

030A00

51

111

15

243A00

46.2

50.0

55.6

60

030A00

62

111

15

14

208/230-3-60 187

253

22.4

149

1.9

10.2

Ċ

Low

Ċ

Ċ

Ċ/Ċ

69.3/ 69.3

90/ 90

Ċ

73/ 73

387/387

Ċ

225A00

20.0/ 23.1

7.5/10.0

69.3/ 69.3

90/ 90

032A00

73/ 73

387/387

18

226A00

30.0/ 34.6

11.3/15.0

69.3/ 69.3

90/ 90

032A00

73/ 73

387/387

18

227A00

50.0/ 57.7

18.8/25.0

81.3/ 90.4

90/100

032A00

75/ 84

387/387

18

228A00

70.0/ 80.8

26.3/35.0

106.3/119.2

110/125

032A00

98/110

387/387

18

230A00

100.1/115.5

37.6/50.0

143.8/133.7

150/150

032A00

132/150

387/387

18

231A00

120.1/138.6

45.1/60.0

168.9/156.8

175/175

032A00

155/177

387/387

18

15.0

High

Ċ

Ċ

Ċ/Ċ

74.1/ 74.1

90/ 90

Ċ

79/ 79

396/396

Ċ

225A00

20.0/ 23.1

7.5/10.0

74.1/ 74.1

90/ 90

032A00

79/ 79

396/396

18

226A00

30.0/ 34.6

11.3/15.0

74.1/ 74.1

90/ 90

032A00

79/ 79

396/396

18

227A00

50.0/ 57.7

18.8/25.0

87.3/ 96.4

90/100

032A00

80/ 89

396/396

18

228A00

70.0/ 80.8

26.3/35.0

112.3/125.2

125/150

032A00

103/116

396/396

18

230A00

100.1/115.5

37.6/50.0

149.8/139.7

150/150

032A00

138/156

396/396

18

231A00

120.1/138.6

45.1/60.0

174.9/162.8

175/175

032A00

161/182

396/396

18

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16

Advertising