Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER

SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

(EA.)

OFM

FLA

IFM
FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

12

(cont)

575-3-60

518

632

6.1

40.0

0.8

2.8

Ċ

Low

Ċ

Ċ

Ċ

20.1

20

Ċ

21

124

Ċ

239A00

13.9

15.0

20.8

25

030A00

21

124

15

240A00

23.1

25.0

32.4

35

030A00

32

124

15

241A00

32.3

35.0

43.9

45

030A00

42

124

15

242A00

37.0

40.0

49.7

50

030A00

48

124

15

243A00

46.2

50.0

49.7

60

030A00

58

124

15

3.3

High

Ċ

Ċ

Ċ

18.6

20

Ċ

20

142

Ċ

239A00

13.9

15.0

21.4

25

030A00

20

142

15

240A00

23.1

25.0

33.0

35

030A00

30

142

15

241A00

32.3

35.0

45.1

45

030A00

41

142

15

242A00

37.0

40.0

50.3

50

030A00

46

142

15

243A00

46.2

50.0

50.3

60

030A00

57

142

15

2.8

3.0

Low

Ċ

Ċ

Ċ

21.1

25

Ċ

23

110

Ċ

239A00

13.9

15.0

24.6

25

030A00

23

110

15

240A00

23.1

25.0

36.1

40

030A00

33

110

15

241A00

32.3

35.0

47.7

50

030A00

44

110

15

242A00

37.0

40.0

53.4

60

030A00

49

110

15

243A00

46.2

50.0

53.4

60

030A00

60

110

15

3.3

High

Ċ

Ċ

Ċ

21.1

25

Ċ

23

110

Ċ

239A00

13.9

15.0

24.6

25

030A00

23

110

15

240A00

23.1

25.0

36.1

40

030A00

33

110

15

241A00

32.3

35.0

47.7

50

030A00

44

110

15

242A00

37.0

40.0

53.4

60

030A00

49

110

15

243A00

46.2

50.0

53.4

60

030A00

60

110

15

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.