Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER
SUPPLY

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

(EA)

OFM

FLA

IFM
FLA

POWER

EXHAUST

FLA

IFM

TYPE

ELECTRIC

HEAT

POWER

SUPPLY

CRSINGLE

PART

NO.

(NOTE3)

DISCONNECT

SIZE

WIRING

FIG.

NO.

MIN

MAX

RLA

LRA

CRHEATER

PART

NO.

FLA

NOMINAL

KW*

MCA

MOCP†

FLA

LRA

05

(cont)

208/230-3-60

(cont)

187

253

14.6

91

0.9

4.9

1.4

Low

Ċ

Ċ

Ċ/Ċ

30.2/30.2

40/40

Ċ

31/31

111/111

Ċ

208A00

10.0/11.5

3.8/ 5.0

30.2/30.2

40/40

030A00

31/31

111/111

15

209A00

15.0/17.3

5.6/ 7.5

32.6/35.0

40/40

030A00

31/33

111/111

15

210A00

20.0/23.1

7.5/10.0

38.9/42.2

40/45

030A00

36/39

111/111

15

211A00

30.0/34.6

11.3/15.0

51.4/56.6

60/60

030A00

47/53

111/111

15

212A00

40.0/46.2

15.0/20.0

63.9/71.0

70/80

031A00

59/66

111/111

16

5.2

High

Ċ

Ċ

Ċ/Ċ

30.5/30.5

45/45

Ċ

31/31

130/130

Ċ

208A00

10.0/11.5

3.8/ 5.0

30.5/30.5

45/45

030A00

31/31

130/130

15

209A00

15.0/17.3

5.6/ 7.5

33.0/35.3

45/45

030A00

31/33

130/130

15

210A00

20.0/23.1

7.5/10.0

39.3/42.6

45/45

030A00

36/40

130/130

15

211A00

30.0/34.6

11.3/15.0

51.8/57.0

60/60

030A00

48/53

130/130

15

212A00

40.0/46.2

15.0/20.0

64.3/71.4

70/80

031A00

59/66

130/130

16

460-3-60

414

506

7.1

46

0.5

2.1

Ċ

Low

Ċ

Ċ

Ċ

13.6

20

Ċ

14

55

Ċ

215A00

5.8

5.0

13.6

20

030A00

14

55

15

216A00

8.7

7.5

16.2

20

030A00

15

55

15

217A00

11.5

10.0

19.8

20

030A00

18

55

15

218A00

17.3

15.0

27.0

30

030A00

25

55

15

219A00

23.1

20.0

34.2

35

030A00

31

55

15

2.6

High

Ċ

Ċ

Ċ

14.1

20

Ċ

14

64

Ċ

215A00

5.8

5.0

14.1

20

030A00

14

64

15

216A00

8.7

7.5

16.8

20

030A00

15

64

15

217A00

11.5

10.0

20.4

25

030A00

19

64

15

218A00

17.3

15.0

27.6

30

030A00

25

64

15

219A00

23.1

20.0

34.8

35

030A00

32

64

15

2.1

0.6

Low

Ċ

Ċ

Ċ

14.2

20

Ċ

14

56

Ċ

215A00

5.8

5.0

14.2

20

030A00

14

56

15

216A00

8.7

7.5

16.9

20

030A00

16

56

15

217A00

11.5

10.0

20.5

25

030A00

19

56

15

218A00

17.3

15.0

27.7

30

030A00

26

56

15

219A00

23.1

20.0

35.0

40

030A00

32

56

15

2.6

High

Ċ

Ċ

Ċ

14.7

20

Ċ

15

65

Ċ

215A00

5.8

5.0

14.7

20

030A00

15

65

15

216A00

8.7

7.5

17.5

20

030A00

16

65

15

217A00

11.5

10.0

21.2

25

030A00

19

65

15

218A00

17.3

15.0

28.4

30

030A00

26

65

15

219A00

23.1

20.0

35.6

40

030A00

33

65

15

575-3-60

518

632

5.0

34.0

0.4

2.0

Ċ

Low

Ċ

Ċ

Ċ

10.7

15

Ċ

11

42

Ċ

221A00

9.2

10.0

16.3

20

030A00

15

42

15

222A00

13.9

15.0

22.1

25

030A00

20

42

15

223A00

18.5

20.0

27.9

30

030A00

26

42

15

High

Ċ

Ċ

Ċ

10.6

15

Ċ

11

48

Ċ

221A00

9.2

10.0

16.1

20

030A00

15

48

15

222A00

13.9

15.0

22.0

25

030A00

20

48

15

223A00

18.5

20.0

27.8

30

030A00

26

48

15

1.4

Low

Ċ

Ċ

Ċ

12.1

15

Ċ

12

44

Ċ

221A00

9.2

10.0

18.0

20

030A00

17

44

15

222A00

13.9

15.0

23.9

25

030A00

22

44

15

223A00

18.5

20.0

29.6

30

030A00

27

44

15

High

Ċ

Ċ

Ċ

12.0

15

Ċ

12

50

Ċ

221A00

9.2

10.0

17.9

20

030A00

16

50

15

222A00

13.9

15.0

23.8

25

030A00

22

50

15

223A00

18.5

20.0

29.5

30

030A00

27

50

15

06

208/230-1-60

187

253

26.9

145

1.5

4.9

Ċ

Low

Ċ

Ċ

Ċ/Ċ

46.1/ 46.1

60/ 60

Ċ

44/ 44

164/164

Ċ

201A00

17.3/ 20.0

3.8/ 5.0

46.1/ 46.1

60/ 60

028A00

44/ 44

164/164

13

202A00

26.0/ 30.0

5.6/ 7.5

46.1/ 48.6

60/ 60

028A00

44/ 46

164/164

13

203A00

34.7/ 40.0

7.5/10.0

54.5/ 61.1

60/ 70

028A00

51/ 57

164/164

13

204A00

52.0/ 60.0

11.3/15.0

76.1/ 86.1

80/ 90

029A00

71/ 80

164/164

14

205A00

69.3/ 80.0

15.0/20.0

97.8/111.1

100/125

029A00

91/103

164/164

14

206A00

86.7/100.0

18.8/25.0

119.4/136.1

125/150

029A00

111/126

164/164

14

7.0

High

Ċ

Ċ

Ċ/Ċ

48.2/ 48.2

60/ 60

Ċ

46/ 46

190/190

Ċ

201A00

17.3/ 20.0

3.8/ 5.0

48.2/ 48.2

60/ 60

028A00

46/ 46

190/190

13

202A00

26.0/ 30.0

5.6/ 7.5

48.2/ 51.3

60/ 60

028A00

46/ 48

190/190

13

203A00

34.7/ 40.0

7.5/10.0

57.1/ 63.8

60/ 70

028A00

53/ 60

190/190

13

204A00

52.0/ 60.0

11.3/15.0

78.7/ 88.8

80/ 90

029A00

73/ 83

190/190

14

205A00

69.3/ 80.0

15.0/20.0

100.4/113.8

110/125

029A00

93/106

190/190

14

206A00

86.7/100.0

18.8/25.0

122.1/138.8

125/150

029A00

113/129

190/190

14

LEGEND

FLA

− Full Load Amps

HACR − Heating, Air Conditioning and Refrigeration
IFM

− Indoor − Fan Motor

LRA

− Locked Rotor Amps

MCA

− Minimum Circuit Amps

MOCP − Maximum Overcurrent Protection
NEC

− National Electrical Code

OFM

− Outdoor−Fan Motor

RLA

− Rated Load Amps

*

Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-

tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%.

Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =

224 + 231 + 226
3

681
3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v

Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if

field−supplied pressure connectors are used.

50PG03−16