Install single point box, Configuring the comfortlink™ control – Carrier 50PG03-16 User Manual

Page 4

Advertising
background image

4

HEATER ASSEMBLY

CONNECT PL3 PLUG

AND RECEPTACLE

ROUTE HEATER POWER WIRES

THROUGH RACEWAY AND BEHIND

COMPRESSORS (COMPRESSORS

REMOVED FOR CLARITY)

POWER WIRES ARE

ROUTED INTO BOTTOM

OF SINGLE POINT BOX

SINGLE

POINT

BOX

C06185

Fig. 4Electric Heater Wire Routing

AFFIX HEATER WIRING LABEL DIAGRAM
SUPPLIED WITH HEATERS ON
FOIL FACE INSULATION IN AREA SHOWN

C06186

Fig. 5Heater Label Location

Install Single Point Box
See Tables 1 and 2 to determine the correct single point box

accessory for the selected heater. The appropriate single point box

is determined by the MOCP (maximum overcurrent protection)

for the heater and unit combination. Refer to the correct figure for

correct installation of the single point box components.
Single point accessories CRSINGLE028A00 and

CRSINGLE030A00 are for use on units where the combined

MOCP rating is less than 60 amps. These accessories contain

only a terminal block; no fuses are provided. Fuses are not

required per the National Electrical Code in these single point

accessories since the circuit is below 60 amps. Field−supplied

pressure connectors (Kerneys) may be used in place of these

single point boxes.
All fuses provided in the single point boxes are rated at 60 amps.

UNIT VOLTAGE

FUSE VOLTAGE RATING

UL CLASS

208/230

250

RK5

460

600

T

575

600

T

To install single point box:

1. Remove single point box access panel located on the end

of the unit. Save panel and screws. (See Fig. 3.)

2. Using the screws provided, install the terminal blocks and

fuse blocks (if required). (See Fig. 6-12.)

3. If required, using the wires provided, connect the terminal

block to the fuse block. (See Fig. 13-22.)

4. Route power wires from the control box and electric

heaters into the single point box. Route power wires from

the disconnect into the single point box through power

entry hole located next to the access panel. Make all

wiring connections.

5. If single point box has fuses, install hinged cover using

rivets provided. Install magnetic latch in rectangular hole.

(See Fig. 7-10 and 12.)

6. Install wiring label on back of single point box access

panel or on hinged cover.

7. Replace single point box access panel removed in item 1.

Configuring the ComfortLink

t Control

The ComfortLink control must be configured for Electric Heat

(default is No Heat). In addition, if a single-stage electric heater

has been installed, it will be necessary to change the N.HTR

configuration (2 is the default setting). These configurations are

changed through the Scrolling Marquee Display or a Carrier

network device.