Step 7 — Orifice Change —

This unit is factory as-

sembled for heating operation using natural gas at an elevation
from sea level to 2000 ft. This unit uses orifice type
LH32RFnnn, where “nnn” indicates the orifice size based on
drill size diameter in thousands of an inch.
HIGH ELEVATION (Above 2000 ft) — Use accessory high
altitude kit when installing this unit at an elevation of 2000 to
7000 ft. For elevations above 7000 ft, refer to Table 2 to identi-
fy the correct orifice size for the elevation. See Table 3 for the
number of orifices required for each unit size. Purchase these
orifices from your local Carrier dealer. Follow instructions in
accessory Installation Instructions to install the correct orifices.

Table 2 — Altitude Compensation*

*As the height above sea level increases, there is less oxygen per

cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes. Includes a 4% input reduction per each 1000 ft.

†Orifices available through your Carrier dealer.

Table 3 — Orifice Quantity

CONVERSION TO LP (Liquid Propane) GAS — Use acces-
sory LP gas conversion kit when converting this unit for use
with LP fuel usage for elevations up to 7000 ft. For elevations
above 7000 ft, refer to Table 4 to identify the correct orifice
size for the elevation. See Table 3 for the number of orifices
required for each unit size. Purchase these orifices from your
local Carrier dealer. Follow instructions in accessory Installa-
tion Instructions to install the correct orifices.

Table 4 — LP Gas Conversion*

*As the height above sea level increases, there is less oxygen per

cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes. Includes a 4% input reduction per each 1000 ft.

†Orifices available through your Carrier dealer.

ELEVATION (ft)

NATURAL GAS ORIFICE†

Low Heat

High Heat

0-1,999

30

29

2,000

30

29

3,000

31

30

4,000

31

30

5,000

31

30

6,000

31

30

7,000

32

31

8,000

32

31

9,000

33

31

10,000

35

32

UNIT

ORIFICE QUANTITY

48TMD016

5

48TMD020,
48TMD024,
48TMD028,
48TMF016

6

48TMF020,
48TMF024,
48TMF028

7

ELEVATION (ft)

LP GAS ORIFICE†

0-1,999

36

2,000

37

3,000

38

4,000

38

5,000

39

6,000

40

7,000

41

8,000

41

9,000

42

10,000

43

INDUCED DRAFT
MOTOR

MAIN BURNER
SECTION

COMBUSTION
FAN HOUSING

HEAT EXCHANGER
SECTION

Fig. 11 — Combustion Fan Housing Location

3/4" FPT DRAIN
CONNECTION

1-3/8"
DRAIN HOLE

Fig. 12 — Condensate Drain Details

(48TM016 Shown)

Fig. 13 — Condensate Drain Piping Details