Table 24 — fan rpm at pulley settings, Table 25 — evaporator-fan motor data, Table 26 — evaporator-fan motor efficiency – Carrier 48TM016-028 User Manual

Page 40

Advertising
background image

40

Table 22 — Air Quantity Limits

Table 23 — Accessory/FIOP Static Pressure (in. wg)* — 48TM016-028

LEGEND

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then

be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

Table 24 — Fan Rpm at Pulley Settings*

*Approximate fan rpm shown.

†Indicates standard drive package.

**Indicates alternate drive package.

††Due to belt and pulley size, pulley cannot be set to this number of turns open.

Table 25 — Evaporator-Fan Motor Data

LEGEND

*Extensive motor and electrical testing on these units ensures that the full

horsepower (brake kilowatt) range of the motors can be utilized with confi-
dence. Using fan motors up to the horsepower (brake kilowatt) ratings shown
in this table will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.

NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992 (EPACT) effec-
tive October 24, 1997.

Table 26 — Evaporator-Fan Motor Efficiency

NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992 (EPACT) effec-
tive October 24, 1997.

UNIT

48TM

MINIMUM

COOLING

CFM

MINIMUM

HEATING CFM

MAXIMUM

CFM

Low Heat

High Heat

016

4500

3800

3800

7,500

020

5400

4750

5450

9,000

025

6000

4750

5450

10,000

028

7000

4750

5450

11,250

COMPONENT

CFM

4500

5000

5400

6000

7200

7500

9000

10,000

11,250

EconoMi$erIV and EconoMi$er2

0.040

0.050

0.060

0.070

0.090

0.100

0.110

0.120

0.140

MoistureMi$er™ Dehumidification

0.045

0.048

0.060

0.071

0.103

0.111

0.160

0.197

0.250

FIOP

Factory-Installed Option

UNIT

48TM

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

016†

††

††

††

††

1021

1002

984

965

947

928

910

891

873

016**

††

††

††

††

1200

1178

1156

1134

1112

1091

1069

1047

1025

020†

††

††

1095

1077

1058

1040

1021

1002

984

965

947

928

910

020**

††

††

1287

1265

1243

1222

1200

1178

1156

1134

1112

1091

1069

025†

††

††

††

††

1151

1132

1114

1095

1077

1058

1040

1021

1002

025**

††

††

††

††

1369

1347

1325

1303

1281

1259

1237

1215

1193

028†

††

††

1283

1269

1247

1225

1203

1182

1160

1138

1116

1095

1066

028**

††

††

††

††

1551

1524

1497

1470

1443

1415

1388

1361

1332

UNIT

48TM

UNIT

VOLTAGE

MAXIMUM

ACCEPTABLE
CONTINUOUS

BHP*

MAXIMUM

ACCEPTABLE
CONTINUOUS

BkW*

MAXIMUM

ACCEPTABLE

OPERATING

WATTS

MAXIMUM

AMP DRAW

016

208/230

6.13

4.57

5,180

15.8

460

7.9

575

6.0

020

208/230

5.90

4.40

5,180

15.8

460

7.9

575

6.0

025

208/230

8.70

6.49

7,915

22.0

460

9.50

7.08

8,640

13.0

575

8.70

6.49

7,915

10.0

028

208/230

10.20

7.61

9,510

28.0

460

11.80

8.80

11,000

14.6

575

10.20

7.61

9,510

13.0

BHP

Brake Horsepower

BkW

Brake Kilowatts

UNIT

48TM

MOTOR EFFICIENCY

(%)

5 Hp

87.5

7.5 Hp

88.5

10 Hp

89.5