Belt tension adjustment, Condenser-fan adjustment, Power failure – Carrier 48TM016-028 User Manual

Page 45: Refrigerant charge

Advertising
background image

45

Belt Tension Adjustment —

To adjust belt tension:

1. Loosen fan motor bolts.
2. Turn motor jacking bolt to move motor mounting plate up

or down for proper belt tension (

3

/

8

in. deflection at

midspan with one finger [9 lb force]).

3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure motor in

fixed position.

Condenser-Fan Adjustment

48TM016,020,028 UNITS (Fig. 52)

1. Shut off unit power supply.
2. Remove access panel(s) closest to the fan to be adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed

across the fan orifice.

5. Tighten setscrews and replace panel(s).
6. Turn on unit power.

48TM025 UNITS (Fig. 53)

1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub

screws.

3. Adjust fan height on unit, using a straightedge placed

across the fan orifice.

4. Tighten setscrews and replace rubber hubcap to prevent

hub from rusting to motor shaft.

5. Fill hub recess with permagum if rubber hubcap is

missing.

Power Failure —

Dampers have a spring return. In event

of power failure, dampers will return to fully closed position
until power is restored. Do not manually operate economizer
motor
.

Refrigerant Charge —

Amount of refrigerant charge is

listed on unit nameplate and in Table 1. Refer to Carrier GTAC
II; Module 5; Charging, Recovery, Recycling, and Reclama-
tion section for charging methods and procedures. Unit
panels must be in place when unit is operating during charging
procedure.
NOTE: Do not use recycled refrigerant as it may contain
contaminants.
NO CHARGE — Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refriger-
ant (refer to Table 1).
LOW CHARGE COOLING — Using cooling charging chart
(see Fig. 54), add or remove refrigerant until conditions of the
chart are met. Note that charging chart is different from those
normally used. An accurate pressure gage and temperature-
sensing device is required. Charging is accomplished by
ensuring the proper amount of liquid subcooling. Measure
liquid line pressure at the liquid line service valve using
pressure gage. Connect temperature sensing device to the
liquid line near the liquid line service valve and insulate it so
that outdoor ambient temperature does not affect reading.
TO USE THE COOLING CHARGING CHART — Use the
above temperature and pressure readings, and find the intersec-
tion point on the cooling charging chart. If intersection point
on chart is above line, add refrigerant. If intersection point on
chart is below line, carefully recover some of the charge.
Recheck suction pressure as charge is adjusted.
NOTE: Indoor-air cfm must be within normal operating range
of unit. All outdoor fans must be operating.

The TXV (thermostatic expansion valve) is set to maintain

between 15 and 20 degrees of superheat at the compressors.
The valves are factory set and should not require re-adjustment.
MOISTUREMI$ER™ SYSTEM CHARGING — The sys-
tem charge for units with the MoistureMi$er option is greater
than that of the standard unit alone. The charge for units with
this option is indicated on the unit nameplate drawing. To
charge systems using the MoistureMi$er dehumidification
package, fully evacuate, recover, and re-charge the system to
the nameplate specified charge level. To check or adjust
refrigerant charge on systems using the MoistureMi$er
dehumidification package, charge per the standard subcooling
charts. The subcooler MUST be deenergized to use the
charging charts. The charts reference a liquid pressure (psig)
and temperature at a point between the condenser coil and the
subcooler coil. A tap is provided on the unit to measure liquid
pressure entering the subcooler (leaving the condenser).

NOTE: Dimensions are in inches.

Fig. 53 — Condenser-Fan Adjustment,

48TM025

NOTE: Dimensions are in inches.

Fig. 52 — Condenser Fan Adjustment,

48TM016,020,028

50

40

100

150

200

250

300

350

400

60

80

100

120

140

ALL OUTDOOR FANS MUST BE OPERATING

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

LIQUID

TEMPERA

TURE

A

T

LIQUID

V

A

L

V

E

(DEG

F)

BOTH CIRCUITS

REDUCE CHARGE IF BELOW CURVE

ADD CHARGE IF ABOVE CURVE

Fig. 54 — Cooling Charging Chart