Install Field-Fabricated Wind Baffles — Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 22 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be

1

/

4

-in. diameter and

5

/

8

-in. long. Drill required screw holes for mounting baffles.

Install Motormaster V Controls — The Motormaster V
(MMV) control is a motor speed control device which adjusts
condenser fan motor speed in response to declining liquid
refrigerant pressure. A properly applied Motormaster V control
extends the operating range of air-conditioning systems and
permits operation at lower outdoor ambient temperatures.

The minimum ambient temperatures at which the unit will

operate are:

To operate down to the ambient temperatures listed,

Motormaster V controls (Fig. 24) must be added. Field-
fabricated and installed wind baffles are also required for all units
(see Fig. 22). The Motormaster V control permits operation of
the unit to an ambient temperature of –20 F (–29 C). The control
regulates the speed of 3-phase fan motors that are compatible
with the control. These motors are factory installed.

See Table 6 for the Motormaster V control accessory

package usage. Table 7 shows applicable voltages and motors.
Replacement of fan motor IS NOT REQUIRED ON
CURRENT PRODUCTION UNITS
since the control is
compatible with the factory-installed fan motors. Only field
wiring control is required.

Install the Motormaster V control per instructions supplied

with accessory.

Table 6 — Motormaster V Control Package Usage

Table 7 — Applicable Voltages and Motors

To avoid damage to the refrigerant coils and electrical com-
ponents, use recommended screw sizes only. Use care
when drilling holes.

TEMPERATURE OPERATING LIMITS — F° (C°)

Standard

Unit

Unit with

Low Ambient Kit

Unit with

MMV Control

40 (4)

25 (–4)

–20 (–29)

UNIT

VOLTAGE

ITEM DESCRIPTION

48TM016-028

208/230

CRLOWAMB015A00

460

CRLOWAMB016A00

575

CRLOWAMB017A00

VOLTAGE

COMPATIBLE MOTOR

208/230-3-60

HD52AK654

460-3-60

HD52AK654

575-3-60

HD52GE576

Fig. 24 — Motormaster® V Control

2 5 6

2

12 13A

13B

13C

1

2

3

TO MOTOR(S)

TO PRESSURE
TRANSDUCER

BLK

YEL

BLU

FROM FUSE BLOCK

B