Carrier 48TM016-028 User Manual

Page 30

Advertising
background image

30

In order to have the CO

2

sensor control the economizer

damper in this manner, first determine the damper voltage out-
put for minimum or base ventilation. Base ventilation is the
ventilation required to remove contaminants during unoccu-
pied periods. The following equation may be used to determine
the percent of outside-air entering the building for a given
damper position. For best results there should be at least a
10 degree difference in outside and return-air temperatures.

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air
T

R

= Return-Air Temperature

RA = Percent of Return Air
T

M

= Mixed-Air Temperature

Once base ventilation has been determined, set the mini-

mum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or

maximum ventilation rate to the building. For example, an out-
put of 3.6 volts to the actuator provides a base ventilation rate
of 5% and an output of 6.7 volts provides the maximum venti-
lation rate of 20% (or base plus 15 cfm per person). Use Fig. 43
to determine the maximum setting of the CO

2

sensor. For ex-

ample, a 1100 ppm set point relates to a 15 cfm per person de-
sign. Use the 1100 ppm curve on Fig. 43 to find the point when
the CO

2

sensor output will be 6.7 volts. Line up the point on the

graph with the left side of the chart to determine that the range
configuration for the CO

2

sensor should be 1800 ppm. The

EconoMi$erIV controller will output the 6.7 volts from the
CO

2

sensor to the actuator when the CO

2

concentration in the

space is at 1100 ppm. The DCV set point may be left at 2 volts
since the CO

2

sensor voltage will be ignored by the

EconoMi$erIV controller until it rises above the 3.6 volt setting
of the minimum position potentiometer.

Once the fully occupied damper position has been deter-

mined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maximum posi-
tion as this can result in over-ventilation to the space and poten-
tial high-humidity levels.

CO

2

Sensor Configuration — The CO

2

sensor has preset

standard voltage settings that can be selected anytime after the
sensor is powered up. See Table 13.

Use setting 1 or 2 for Carrier equipment. See Table 13.

1. Press Clear and Mode buttons. Hold at least 5 seconds

until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See

Table 13.

4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.

The custom settings of the CO

2

sensor can be changed any-

time after the sensor is energized. Follow the steps below to
change the non-standard settings:

1. Press Clear and Mode buttons. Hold at least 5 seconds

until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu

and press Enter.

4. Use the Up/Down button to toggle through each of the

nine variables, starting with Altitude, until the desired set-
ting is reached.

5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to

continue to the next variable.

Dehumidification of Fresh Air with DCV Control — Infor-
mation from ASHRAE indicates that the largest humidity load
on any zone is the fresh air introduced. For some applications,
a field-installed energy recovery unit can be added to reduce
the moisture content of the fresh air being brought into the
building when the enthalpy is high. In most cases, the normal
heating and cooling processes are more than adequate to re-
move the humidity loads for most commercial applications.

If normal rooftop heating and cooling operation is not ade-

quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.

Table 13 — CO

2

Sensor Standard Settings

LEGEND

ppm — Parts Per Million

(T

O

x

OA

) + (TR x

RA

) = T

M

100

100

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL RANGE

(ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Interface with Standard
Building Control System

Proportional

Any

0-10V

4-20 mA

0-2000

1000

50

2

Proportional

Any

2-10V

7-20 mA

0-2000

1000

50

3

Exponential

Any

0-10V

4-20 mA

0-2000

1100

50

4

Economizer

Proportional

15

0-10V

4-20 mA

0-1100

1100

50

5

Proportional

20

0-10V

4-20 mA

0- 900

900

50

6

Exponential

15

0-10V

4-20 mA

0-1100

1100

50

7

Exponential

20

0-10V

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

0-10V

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/
Loading Docks

Proportional

0-10V

4-20 mA

0-2000

700

50

Advertising