Table 5 — Electrical Data

LEGEND

*Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination

load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker. Canadian units
may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.

Use the following formula to determine the percent

voltage imbalance.

% Voltage Imbalance

EXAMPLE: Supply voltage is 460-3-60.

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

UNIT

48TM

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 1A

No. 2

Min

Max

RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea)

Hp

FLA

FLA LRA

FLA

MCA

MOCP*

016

208/230

187

253

32.1

195

20.7

156

3

0.5

1.7

5.0 15.8/15.8

0.57

82/82

110/110

4.6

18.8

0.57

86/86

110/110

460

414

508

16.4

95

10

70

3

0.5

0.8

5.0

7.9

0.30

41

50

2.3

6.0

0.30

43

50

575

518

633

12

80

8.2

54

3

0.5

0.75

5.0

6.0

0.57

31

40

2.1

4.8

0.57

34

40

020

208/230

187

253

30.1

225

28.8

195

3

0.5

1.7

5.0 15.8/15.8

0.57

87/87

110/110

4.6

18.8

0.57

92/92

110/110

460

414

508

15.5

114

14.7

95

3

0.5

0.8

5.0

7.9

0.30

44

50

2.3

6.0

0.30

47

60

575

518

632.5 12.1

80

10.7

80

3

0.5

0.75

5.0

6.0

0.57

34

40

2.1

4.8

0.57

36

40

025

208/230

187

253

42

239

33.6

225

2

1

6.6

7.5 25.0/25.0

0.57

124/124

150/150

4.6

18.8

0.57

129/129

150/150

460

414

508

19.2

125

17.3

114

2

1

3.3

7.5

13.0

0.30

61

80

2.3

6.0

0.30

63

80

575

518

633

13.8 80.0

13.5

80.0

2

1.0

3.4

7.5

10.0

0.57

48

60

2.1

4.8

0.57

50

60

028

208/230

187.2

253

20.7

156

20.7

156

47.1

245

6

0.5

1.7

10.0 28.0/28.0

0.57

138/138

175/175

4.6

18.8

0.57

143/143

150/175

460

414

508

10

75

10

75

19.6

125

6

0.5

0.8

10.0

14.6

0.30

64

80

2.3

6

0.30

66

80

575

517.5 632.5

8.2

54

8.2

54

15.8

100

6

0.5

0.8

10.0

13.0

0.57

54

60

2.1

4.8

0.57

56

70

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

AB = 452 v
BC = 464 v
AC = 455 v

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.