Step 14 — Install Humidistat for Optional
MoistureMi$er™ Package —

MoistureMi$er dehu-

midification package operation can be controlled by field
installation of a Carrier-approved humidistat. To install the
humidistat perform the following procedure:

1. Locate humidistat on a solid interior wall in the condi-

tioned space. Location should be a well ventilated area
to sense average humidity.

2. Route thermostat cable or equivalent single leads of col-

ored wire from Humidistat terminals through conduit in
unit to the low voltage connection on the 2-pole terminal
strip (TB3) as shown in Fig. 44 and Fig. 45. See Fig. 46
for operational diagram.

Fig. 45 — Typical MoistureMi$er Dehumidification

Package Control Box

Fig. 44 — Typical MoistureMi$er Dehumidification Package

Humidistat Wiring Schematic (460 V Unit Shown)

GRN-YEL

24V

TRAN1

RED

BLK

YEL

ORN

A

C

GRN-YEL

24V

TRAN3

RED

BLK

YEL

ORN

A

C

YEL

BLK

BLK

BLK

TO CRANKCASE
HEATER CIRCUITS

YEL

BLK

21

11

BLK

BLK

TB3

S-LPS1

S-LPS2

LLSV1

LLSV2

1

2

CB4

3.2 AMPS

FACTORY INSTALLED JUMPER

(OR HUMIDISTAT IF USED)

MOISTUREMI$ER

LEGEND

CB

Circuit Breaker

LLSV — Liquid Line Solenoid Valve
LPS

Low-Pressure Switch

TB

Terminal Block

TRAN — Transformer