Refer to ignition module

illustration, is there 120VAC

between

P1(1) and P1(3)?

Is front panel power

switch light on,

indicating power?

Y

N

Position front panel

power switch to

“ON” position.

Is there 120VAC

across switch?

(see photo at right)

Light burned out,

replace switch.

Y

Is there 120VAC

across terminal block?

(see photo at right)

N

Determine power

source problem and

correct.

Repair/replace wire

harness to switch.

Y

N

Is ignition module

power light on?

N

Y

Refer to ignition module

illustration, is there 120VAC

going to module at locations

P7(1) and P7(3)?

N

Replace ignition module.

(see “Ignition Module Replacement”)

Replace transformer.

(see “Transformer Replacement”)

N

N

Y

Y

Is ignition module

power and flame light

flashing?

Reset heater by

interrupting power.

Reestablish power and

Adjust thermostat to

call for heat,

tank must be cold.

Allow heater to run

through heating cycle.

Did heater complete

heating cycle and did

blower post purge?

See next page

System is OK.

Supply voltage polarity

is incorrect.

Y

N

N

Y

Refer to ignition module

illustration, is there 24VAC

going to module at locations

P2(1) and P2(2)?

System Observation

For models with Hot Surface Ignition

IGNITION MODULE

WARNING

120 volt potential exposure. Use caution

making voltage checks to avoid personal injury.

16

Power Switch

Terminal Block

Replace ignition module.

(see “Ignition Module Replacement”)

16