Refer to ignition module

illustration, Is there 24VAC

between

P3(7) and P3(8)?

Y

OK, thermostat is

calling for heat.

Turn off power to heater.

Disconnect YELLOW and RED wires from the

thermostat board at location N.O. and COM shown in

photo at right. Use a jumper to connect these two

wires together as shown in photo at right.

Restore power to heater.

Did heater cycle on?

N

Check thermostat sensor

for proper resistance

(OHMS) across blue wires.

(See Appendix A, sensor

resistance)

Are readings correct?

(see photo at right)

Check temperature dial for

proper resistance (OHMS)

(See Appendix B,

temperature dial resistance)

Are readings correct?

(see photo at right)

Y

Y

Replace

thermostat sensor.

(see Thermostat Sensor

Replacement Procedure)

Replace temperature dial

(potentiometer).

(see Thermostat Potentiometer

Replacement Procedure)

N

N

N

Replace thermostat

circuit board.

(see Thermostat Board

Replacement Procedure)

Y

Check sensor harness

continuity.

Is there continuity?

Check temperature dial

harness continuity.

Is there continuity?

Replace harness.

Y

N

Replace harness.

N

Y

See page 39

IGNITION MODULE

IMPORTANT NOTE: This procedure assumes a cool tank

Rotate temperature

dial to highest setting.

Thermostat

not calling

WARNING

120 volt potential exposure. Use

caution making voltage checks

to avoid personal injury.

For models with Hot Surface Ignition

37

Thermostat

Sensor

Temperature Dial

Yellow & Red

wires shown

jumpered

Yellow Wire

(COM)

Red Wire

(N.O.)