Bradford White EF-100T-399-3X User Manual

Page 26

Advertising
background image

Accessing Service Mode on Control Display

For models with Honeywell Integrated Control

To Display Flame Sense Current of the Pilot Flame Sensor:
The pilot flame sense current is available only when the burners are in operation. Step 1: Make sure the status displays

“Heating” or draw enough hot water to start the burners. Step 2: Enter the “Service Mode” described previously. Step 3:

Press the “Select” button until a number value is displayed with “Flame Current” to the right of the number. The value

displayed is in microamps (µA).

SELECT

SET

Status Operational

Flame

Current

Heating

µA

To Display and Change Temperature Setpoint:
Step 1: In “Service Mode” press the “Select” button until “Setpoint” is shown in the water heater display

SELECT

SET

Status

°F

idle

setpoint

Operational

26

26