Check Exhaust Tube Pressure

Blocked Vent Pressure Switch Testing and

Replacement for serial number “CF” and later

Exhaust Tube

pressure tap location

Exhaust tube

at bottom of heater

N

Replace

blocked vent switch.

(see “Blocked Vent

Switch Testing and

Replacement”)

Is exhaust venting

system blocked or

obstructed? Also

check condensate

elbow and drain.

Clear obstruction.

Determine cause

and correct.

Y

Is vent system total

length compliant with

vent tables in the

instruction manual?

Reconfigure vent

system to be

compliant with

vent tables (see

“Specifications”).

Y

N

With monometer, take a

reading at the

exhaust

tube pressure tap location.

Is value negative (-) or

slightly postitive

(see illustration below).

Y

N

With ohmmeter check

pressure switch for

continuity. Contacts should

be closed.

Y

N

Pressure switch O.K.

58

Is pressure in exhaust tube near 2.7" w.c. or more? If so, correct

blockage (above). If exhaust pressure is low (0.40" or less),

replace pressure switch.