3 typical muting application and sensor connection, 4 muting direction – Pilz PSEN op4F-A-14-180/1 User Manual

Page 46

Advertising
background image

PSEN op4F/H-A series

OPERATING MANUAL

46

1003067-EN-02

7.7.3 Typical muting application and sensor connection

Fig. 41 – Typical muting application

The diagram above shows a typical muting application: the protection device installed on the
conveyor must allow the package to pass through but not the operator. The light curtain
temporarily suspends its safety function when the sensors A11, A21, A12, A22 are activated
in the correct sequence.
These may be optical or mechanical sensors that switch 24 V when the object is detected.

7.7.4 Muting direction

The light curtain can be used for bidirectional muting (T-type, four sensors) as well as one-
directional muting (L-type, two sensors).

• T-muting is used when objects can move through the light curtain in both directions.

• L-muting is used when objects move only in one direction.


In BCM mode the maximum activation delay between MUTING1 and MUTING2 (T12max) is
4 seconds
T-Muting
With T-type operation, the device switches to the muting function if the signal from the
MUTING2 input switches within a fixed T12max, after the MUTING1 signal has switched (or
vice versa). The muting function ends as soon as the signal at MUTING1 or MUTING2 goes
low. Users can set the maximum activation delay between MUTING1 and MUTING2 (or vice
versa) from a minimum of 1 second to a maximum of 16 seconds (T12max). Once this time
has elapsed, if users wish to switch to muting status they will need to deactivate the muting
input and start the sequence again.

A11

A12

A21

A22

Safety sensor

Advertising