PSEN op4F/H-A series

OPERATING MANUAL

50

1003067-EN-02

7.7.5 Muting timeout

The muting timeout describes the time for the maximum duration of the muting function; once
the timeout has elapsed, muting is ended.
Users have the option to set this time in BCM as well as ACM mode.
In BCM mode they can select the timeout to be 10 minutes long or infinite; “infinite” means
that the muting timeout may potentially never end: as long as the muting conditions are
present, the muting function will be maintained.

NOTE: This does not comply with the standard IEC 61496-1 and the user is
informed of this fact via a message

Fig. 46 – Muting timeout

Users have the option in the ACM mode set the muting timeout in increments of 1 minute
between 10 min und 1080 min. Alternatively, it can also be set to be infinite.

BCM configuration: Muting timeout

P

W

R

O

S

S

D

E

DM

A

CM

LEVEL

10 min

LED 7 ON green

Infinite

LED 7 OFF

ACM configuration: Muting-Timeout

NOTE: The infinite timeout option does not comply with the standard
IEC 61496-1 and the user is warned accordingly.