51

Network
Installation

FIG. 143: SELECTING THE INPUT AND OUTPUT

SIZE

NOTE:

The HI 3000 Series Input and Output Sizes are
expressed in words. Many of the Profibus Net-
work Management software Input and Output
Sizes are expressed in bytes. Make sure that the
Input/Output selection matches the Input and
Output Sizes of the HI 3000 Series Instruments.

Step 8. Select the Input and Output Sizes that match the

Input and Output Size setup in the HI 3000 Series
Instrument. You can also use a combination of
selections that add up to the desired length. The
Output and Input Sizes have a range from 0 to 122
words. The combined Output and Input Sizes can-
not exceed 208 words.

Step 9. In our example the Input and Output Size set in the

HI 3000 Series instrument is 64 words. In this case
the Input and Output Sizes are equal so we selected
the IN/OUT:128Byte (64 word).

Step 10. Highlight Slot 1. Double click on IN/OUT:128Byte

(64 word). The Input and Output appear in Slot 1
and Slot 2 listing the Module, Order Number and
the I Address (Input Address) and Q Address (Out-
put Address).

Step 11. The HI 3000 Series (ANYBUS) module appears in

the Profibus Network. (See Fig. 144)

FIG. 144: ANYBUS-S PDP APPEARS IN THE

NETWORK

Step 12. Click on the Down Load Icon to download the con-

figuration to the PLC. (See Fig. 145) The Select
Destination Module dialog box appears. (See Fig.
146)

FIG. 145: DOWNLOADING HI 3000 SERIES

CONFIGURATION

Download Button