KEYENCE FS-21X User Manual

Page 3

Advertising
background image

3

Display Selection (Access Mode: EASY)

Excess

gain

Output

status

Power

mode status

PV

CV

Press

Press

CV

Press

• The CV is displayed in

percent based on the
PV.

• The current value will be

displayed if no keys are operated
for approximately 30 s.

• If the timer function is set, the

output status with power mode
and the timer mode with set time
will be displayed alternately.

Display Selection (Access Mode: FULL)

Press

Press

CV

Peak value

Bottom value

LED bar

indicator

Output

status

Peak

excess

gain

Bottom
excess

gain

Power

mode status

Press

Press

Press

Press

Excess

gain

PV

CV

CV

Menu Selection (Access Mode: EASY)

Access mode
selection

Power mode
selection

Timer function
setting

Press

Press manual
button to select

Press manual
button to select

Press the
mode button 3 s min

Press

Other than

F I N E

TURBO

SUPER
TURBO

Press

Press

Press to manual button to
make timer adjustments

* For timer values, refer to the

corresponding table under FULL
mode.

Normal
operation use

Timer OFF (for
normal operation use)

OFF-delay timer

ON-delay timer

One-shot timer

Used if the sensing
distance is insufficient
while the sensor is in
fine mode.

Used if the sensing
environment is bad
due to dust or other
obstacles.

Menu Selection (Access Mode: FULL)

Press the
mode button 3 s min

Access
mode
selection

Power
mode
selection

Select

Select

Select

Select

Edge
detection
mode
selection

Select

Select

S-APC
mode
setting

FINE

TURBO

SUPER TURBO

ULTRA TURBO

HIGH SPEED

HIGH RESO-
LUTION

Timer
function
setting

Power save
function
setting

Shift
function
setting

Press

Press

Press

Used to detect sensing objects highly
precisely under clean environments.

OFF (for normal operation use)
Rising edge
Falling edge

OFF (for normal operation use)
ECO half
ECO all

OFF (for normal operation use)
Shift ON

OFF (for normal operation use)

Press

Timer adjustments

* A maximum error of ±10% of the PV.

Timer adjustment range

Press

Press

Press

Press

Press

Shift value

CV

Shift value adjustment

1~30ms
30~50ms
50~200ms
200~500ms

1-ms increments
2-ms increments
10-ms increments
50-ms increments

Power mode
,

Other than
Power mode
,

Other than
Power mode

Power mode

Other than

Normal operation use

Used if the incident is insufficient while
the sensor is in SUPER TURBO mode.

Used to detect sensing objects
moving at high speed.
Used to detect delicate differences
within a short sensing distance.

Timer OFF (for normal operation use)

OFF-delay timer

ON-delay timer

One-shot timer

Used if the sensing distance is insufficient
while the sensor is in fine mode.
Used if the sensing environment is
bad due to dust or other obstacles.

Sensitivity Settings in Edge Detection Mode
The sensitivity of the sensor will be set to maximum by pressing the
while the sensor is in edge detection mode. Make fine sensitivity adjust-
ments by pressing the

.

Note:

• Press the mode button (

) for a minimum of three seconds to return to the display of the CV from any menu selection stage. To return to the

previous display, press the mode button (

) first, and press the left side (

) of the manual button (

).

• When the power mode is set to HIGH RESOLUTION, the S-APC mode will be always turned ON.
• When the power mode is set to HIGH SPEED, the S-APC mode will be always turned ON in the case of the R model, or otherwise the S-APC mode

will be always turned OFF.

Advertising