3

3

Mount the attached end units (OP-26751: a set of two pieces) on both sides of the
sensor amplifier and the DeviceNet Compatible Network Unit DL-DN1, then fix
the end units with screws on the upper part of each end unit (2 points x 2 units).
The mounting method of the end unit is the same as that of the DeviceNet Compatible
Network Unit DL-DN1.

z

Connecting to a panel mounting type sensor amplifier

1

Connect the sensor amplifier to the DeviceNet Compatible Network Unit DL-DN1
using the optional expansion cable (OP-35361).

2

Detach the sensor amplifier connector (for DIN rail mounting type) of the
DeviceNet Compatible Network Unit DL-DN1 with pliers and mount the attached
expansion connector sticker.

z

Connecting to a large display type sensor amplifier

1

Connect the sensor amplifier to the DeviceNet Compatible Network Unit DL-DN1
using the optional expansion cable (OP-35361).

2

Detach the sensor amplifier connector (for DIN rail mounting type) of the
DeviceNet Compatible Network Unit DL-DN1 with pliers and mount the attached
expansion connector sticker.

Wiring

Use the following procedures to wire the DL-DN1.
Refer also to the DeviceNet Installation Manual published by ODVA.

„

Connecting to DeviceNet

Use the following procedure to connect the DL-DN1 to the DeviceNet.

z

Recommended Cables

For connection between the DL-DN1 and the DeviceNet, use DeviceNet cables conform-
ing to the DeviceNet specifications or dedicated flat cables.

z

Trimming the Cable

1

Strip the cable sheath.
Strip approximately 70 mm of cable sheath.
Make sure that the bare part of the shield braid is 6 mm or shorter.

2

Install shrinkable tube.
Cover the exposed sheathed conductors and the sheath using a shrinkable tube
approximately 40 mm long.

3

Strip the sheathed conductors.
Strip approximately 10 mm of sheath from the end of each conductor.

z

Connecting the Cable

Use the following procedures to wire to the DeviceNet connector supplied with the DL-DN1.

1

Connect the trimmed cable to the DeviceNet connector.
Insert the cable completely.

2

Attach the DeviceNet connector to the DL-DN1.
Plug the connector into the DL-DN1 and secure it down with the screws on each end.
(Tightening torque: 0.2 to 0.3 N‚m)

Be sure to insert the DeviceNet Compatible Network Unit DL-DN1
to the sensor amplifier to the end. Turning on the power with
diagonal insertion or improper insertion may damage the
equipment.

•

Turn OFF the power before connecting the expansion cable

and connect securely. Diagonal or otherwise improper

insertion may damage the equipment.

•

Inserting or pulling the cable when the power is turned ON

may damage the equipment.

•

Turn OFF the power before connecting the expansion cable

and connect securely. Diagonal or otherwise improper

insertion may damage the equipment.

•

Inserting or pulling the cable when the power is turned ON

may damage the equipment.

End unit

End unit

NOTICE

Detach the protection sticker

Expansion cable (cable length: 300 mm)

NOTICE

Sensor amplifier connector
(for DIN rail mounting type)

Expansion
connector sticker

Detach the
protection sticker

Detach the
protection
sticker

Expansion cable (cable length:300mm)

NOTICE

Sensor amplifier connector
(for DIN rail mounting type)

Expansion
connector sticker

Turn off the power before wiring.

To ensure normal communication, use only the DeviceNet or
dedicated cables.

•

If you are using solderless terminals, perform cable wiring /

trimming appropriately to suit the specifications of the

particular terminals.

Recommended solderless terminals: Phoenix Contact's A/AI

Series

•

Do not perform soldering (pre-soldering) on the trimmed

end of the cable.

Point

Point

6 mm or shorter

Approx. 70mm

Shield braid

Sheath

Approx. 40mm

Shrinkable tube

Sheath

Approx. 10mm

Sheathed conductor

Point

Wire color Signal name

Function

Black

Connects 0 V of the
communication power supply.

Blue

CAN_L

Communication signal (Low)

Bare wire

SHIELD

Connects the shield of the
DeviceNet cable.

White

CAN_H

Communication signal (High)

Red

V+

V-

Connects 24 VDC of the
communication power supply.

Black

Blue

White

Red

Advertising